JOHNSON CONTROLS
99
SECTION 7 – MAINTENANCE
FORM 155.35-ICOM2.EN.CE/GB (1018)
DATE: 10/30/2018
7
Blower Fan Manual Stop
1. Navigate to the Control Panel Setting screen.
2. Press the Blower Fan
Stop
button.
LD26800d
After maintenance of the air purge blower fan is com-
plete, be sure to press the Blower Fan
Auto
button. If
the chiller-heater continues to operate with the blower
fan in
STOP
mode, damage and failure of the unit may
result.
EXHAUST GAS CONTAMINANTS
TABLE 21 -
EXHAUST GAS CONTAMINANTS
CONTAMINANT NAME
ALLOWABLE RANGE
MEASUREMENT METHOD
1
Soot
50 mg per Nm3
1
Dust density
2
Nitrogen Oxide
600 ppm
1
Chemiluminescence
2
3
Sulfur Oxide
0 ppm
Non dispersive Infrared gas
analyzer
2
4
Suspended particulate matter
0.5 mg per Nm3
• Liquid sampling
• Filter with membrane filter
• Weight
3
5
Solid carbide
0.5 mg per Nm3
• Filter sampling
• Weight
6
Oil
0.3 mg per Nm3
• Filter sampling
• Carbon tetrachloride extraction
• Infrared ray absorption spectrum
7
Ammonia
0 ppm
Indophenol blue absorptiometry
1. Or within local regulations
2. Converted with 0
2
equal to 0%
3. Not including a glass fiber-shaped material abundantly
Exhaust Gas Chimney Requirements
Each exhaust gas chiller-heater MUST have its own
chimney. This helps prevent the possible contamina-
tion of the chiller-heater by rust or other particulates
that may clog filters.
Содержание YHAU-CE
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 84: ...JOHNSON CONTROLS 84 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...