SECTION 7 – MAINTENANCE
FORM 155.35-ICOM2.EN.CE/GB (1018)
DATE: 10/30/2018
7
PART NAME
LIFESPAN AND REPLACEMENT
INTERVAL
REMARKS
Solution or refrigerant pump shut
off valve
Every 48,000 hours
Temperature controller (TIC)
Every 30,000 hours
Sequencer unit
Every 30,000 hours
Relay
Timer
Fuse
DC power unit
Magnetic contactor, thermal relay
Battery for sequencer unit
Every 5 years
Battery for touch panel
Touch panel
Every 30,000 hours
Inverter (option)
Fan for control panel
Differential pressure switch
Pressure sensor
Pressure switch
Resistance Temperature detector
Thermocouple
LD26803
Exhaust Gas
Absorption Chiller
(One Exhaust Gas
Outlet Flange)
Exhaust Gas
By-pass Damper
Exhaust Gas
Inlet Damper
Purge Blower
Other equipment shall be
prepare by customer
Cooling
Water
Chimney
Gas Engine
Radiation Heat Exchanger
(out of scope)
Temperature gauge (or sensor)
Pressure gauge
Expansion joint
Chilled
Water
Exhaust Gas
Outlet Damper
Cooling
Tower
Scope of supply
FIGURE 37 -
CHILLED / HOT WATER, COOLING WATER AND WASTE EXHAUST GAS SYSTEM
(EXAMPLE OF ONE EXHAUST GAS OUTLET FLANGE)
Содержание YHAU-CE
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 84: ...JOHNSON CONTROLS 84 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...