MANUAL OVERRIDE Key Operation
If the MANUAL OVERRIDE key is pressed during a
schedule shutdown, the STATUS display will display the
message below. This indicates that the Daily Schedule
is being ignored and the chiller will start when chilled
liquid temperature allows, Remote Contacts, UNIT
switch and SYSTEM switches permitting. This is a pri-
ority message and cannot be overridden by anti-recycle
messages, fault messages, etc. when in the STATUS
display mode. Therefore, do not expect to see any other
STATUS messages when in the MANUAL OVERRIDE
mode. MANUAL OVERRIDE is to only be used in
emergencies or for servicing. Manual override mode
automatically disables itself after 30 minutes.
Содержание YCAV1039
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM4 1020 43 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM4 1020 55 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM4 1020 67 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 83: ...83 JOHNSON CONTROLS FORM 201 21 NM4 1020 83 JOHNSON CONTROLS 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 229: ...229 JOHNSON CONTROLS FORM 201 21 NM4 1020 229 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM4 1020 249 JOHNSON CONTROLS 8 This Page intentionally left blank ...
Страница 277: ...277 JOHNSON CONTROLS FORM 201 21 NM4 1020 277 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 308: ...308 JOHNSON CONTROLS FORM 201 21 NM4 1020 308 JOHNSON CONTROLS MAINTENANCE NOTES ...
Страница 309: ...309 JOHNSON CONTROLS FORM 201 21 NM4 1020 309 JOHNSON CONTROLS 9 NOTES ...