270
JOHNSON CONTROLS
FORM 201.21-NM4 (1020)
270
JOHNSON CONTROLS
MICRO PANEL
DEFAULT PROGRAMMABLE VALUES
To quickly program or reset most of the user program-
mable values to their default values, press PROGRAM,
6140, ENTER. The following message will then be
displayed, allowing a choice to reset the operating pa-
rameters to their default values.
YES or NO may be selected for XXX using the
◄
and
►
(ARROW) keys to change the selection.
Following is a list of the operating parameters that will
be reset to their default values:
·
Suction Pressure Cutout = 24.0 PSIG
·
Low Ambient Air Temp Cutout = 25°F
·
Leaving Chilled Liquid Temp Cutout = 36°F
·
High Motor Current Limit = 100%
·
Pulldown Current Limit = 100%
·
Pulldown Current Limit Time = 0 Min.
·
Suction Superheat Setpoint = 10°F
·
Sound limit Setpoint = 0%
DEFAULTS SET PROG VALUES TO DEFAULT?
◄ ►
XXX
Содержание YCAV1039
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM4 1020 43 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM4 1020 55 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM4 1020 67 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 83: ...83 JOHNSON CONTROLS FORM 201 21 NM4 1020 83 JOHNSON CONTROLS 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 229: ...229 JOHNSON CONTROLS FORM 201 21 NM4 1020 229 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM4 1020 249 JOHNSON CONTROLS 8 This Page intentionally left blank ...
Страница 277: ...277 JOHNSON CONTROLS FORM 201 21 NM4 1020 277 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 308: ...308 JOHNSON CONTROLS FORM 201 21 NM4 1020 308 JOHNSON CONTROLS MAINTENANCE NOTES ...
Страница 309: ...309 JOHNSON CONTROLS FORM 201 21 NM4 1020 309 JOHNSON CONTROLS 9 NOTES ...