233
JOHNSON CONTROLS
8
HISTORY KEY
LD10605
HISTORY
KEY
HISTORY Key Operation
The HISTORY key provides the user access to many
unit and system operating parameters captured at the
instant a unit or system safety (fault) shutdown occurs.
The history buffer will also capture system data at the
time of normal shutdowns such as cycling shutdowns.
When the HISTORY key is pressed the following screen
is displayed:
The
◄
and
►
(ARROW) keys allow choosing between
NORMAL SHUTDOWNS and FAULT SHUTDOWNS.
“Fault” shutdowns provide information on safety
shutdowns, while “Normal” shutdowns provide chiller
cycling information on temperature (demand), cycling,
remote, system switch, etc., shutdowns that are non-safe-
ty related shutdowns. Once the selection is made, the
√ (ENTER) key must be pressed to enter the selection.
HISTORY
CHOOSE HISTORY TYPE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
NORM HIST XX 18-JUN-20004 10:34:58 AM
SYS X COOLING DEMAND SHUTDOWN
NORM HIST XX 18-JUN-20004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
Normal Shutdowns History
If the NORMAL SHUTDOWNS History is selected,
the following screen will be displayed:
XX is the normal shutdown number. The display will
provide date and time of the shutdown and the reason
for the cycling shutdown (YYY….).
The operator can view any of the stored 20 single display
normal shutdown history buffers. History buffer number
1 provides the most recent shutdown information and
buffer number 20 is the oldest safety shutdown informa
-
tion saved. The
◄
and
►
(ARROW) keys allow scrolling
between each of the history buffers. The
►
(ARROW)
key scrolls to the next normal history shutdown and the
◄
(ARROW) key scrolls to the previous normal history
shutdown.
The following display will typically be displayed on a
normal shutdown due to shutdown on lack of cooling
demand.
Содержание YCAV1039
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM4 1020 43 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM4 1020 55 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM4 1020 67 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 83: ...83 JOHNSON CONTROLS FORM 201 21 NM4 1020 83 JOHNSON CONTROLS 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 229: ...229 JOHNSON CONTROLS FORM 201 21 NM4 1020 229 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM4 1020 249 JOHNSON CONTROLS 8 This Page intentionally left blank ...
Страница 277: ...277 JOHNSON CONTROLS FORM 201 21 NM4 1020 277 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 308: ...308 JOHNSON CONTROLS FORM 201 21 NM4 1020 308 JOHNSON CONTROLS MAINTENANCE NOTES ...
Страница 309: ...309 JOHNSON CONTROLS FORM 201 21 NM4 1020 309 JOHNSON CONTROLS 9 NOTES ...