Optimized IPLV Fan Control
90
95
100
105
110
115
120
125
130
135
140
145
150
155
75
85
95
105
115
125
Ambient Air Temp (°F)
Di
sc
ha
rg
e
Pr
essu
re
(PS
IG
)
Fan On Press
Fan Off Press
`
LD10634
FIG. 43 - HIGH IPLV FAN CONTROL
High VSD Cabinet Ambient Temperature
Fan Operation
All condenser fans on all systems will run when the
chiller is off and enabled to run, if the VSD internal
ambient temperature is higher than 5°F below the VSD
Cabinet Ambient Temperature Cutout of 158°F (158°F
- 5°F = 153 °F). When the fans turn on in this situa-
tion, the fan outputs will cycle one at a time with a 100
ms delay between fan starts. When the VSD internal
ambient falls below the “Restart Temperature” (158°F
Cutout - 10°F = 148 °F), the fans will all be turned off
without a delay.
VSD TEMPERATURE CONTROL, OPERATION OF THE COOLANT PUMP,
AND VSD CABINET COOLING FANS
The Coolant pump and VSD Cabinet Cooling Fans will
run to cool the VSD whenever any of the following
conditions are met:
·
VSD Comp IGBT Baseplate Temperature on a com-
pressor unit is greater than 10°F below the cutout
(Cutout [218°F]-10°F =208°F). When the VSD
internal ambient falls below the restart temperature
(Cutout [218°F] - 15°F = 203°F), the fans and pump
will turned off without a time delay.
·
VSD Comp IGBT Baseplate Temperature on a 3
compressor unit is greater than 10°F below the
cutout (Cutout [232°F] - 10°F = 222°F). When
the VSD internal ambient falls below the restart
temperature (Cutout - 15°F = 217°F), the fans and
pump will be turned off without a time delay.
·
Pre-charge Enable 1 from the Chiller Logic Board
is ON.
·
Pre-charge Enable 2 from the Chiller Logic Board
is ON.
·
VSD Internal Ambient Temp > 158°F (Cutout)
– 10°F = 148°F. When the Internal Ambient Temp
falls < 158°F (Cutout) - 15°F = 143 °F the VSD
cooling fans and glycol pump will turn off.
·
Condenser Fans (as needed) and VSD coolant pump/
fans will run whenever a compressor is running.
Under these conditions, the condenser fans will run
to control discharge pressure and the VSD coolant
pump/fans will run to cool the IGBT baseplate and
internal cabinet. Additional condenser fans will be
brought on, if the IGBT baseplate temperatures or
internal cabinet ambient rises to 5°F below the cut-
out. Condenser fans will turn off, if the compressor
turns off provided VSD cooling is not required. The
glycol pump and cabinet fan may continue to run,
if VSD cooling is required.
·
Glycol Pump and Cabinet Cooling Fans will also
run in the Service Mode if the Fan/Pump Run Bit
is Set.
CONDENSOR FAN CONTROL (CON'T)
timing when the discharge pressure rises above the Fan
ON Press. The fan stage is decremented, unless the 5
second timer between fan stages is still timing when
the discharge pressure falls below the Fan OFF Press.
When a fan stage is incremented, the fan delay timer is
set to 5 seconds, and the Fan ON pressure is ramped 20
PSIG over the original ON, point back to the original
value over the next 20 seconds. When a fan stage is
decremented, the fan delay timer is set to 5 seconds,
and the Fan OFF pressure is ramped 20 PSIG below the
original Fan OFF point, back to the original value over
the next 20 seconds. The ON and OFF points will vary
as ambient temperature changes. FIG. 43 shows the fan
ON and OFF points relative to ambient temperature.
Содержание YCAV1039
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM4 1020 43 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM4 1020 55 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM4 1020 67 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 83: ...83 JOHNSON CONTROLS FORM 201 21 NM4 1020 83 JOHNSON CONTROLS 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 229: ...229 JOHNSON CONTROLS FORM 201 21 NM4 1020 229 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM4 1020 249 JOHNSON CONTROLS 8 This Page intentionally left blank ...
Страница 277: ...277 JOHNSON CONTROLS FORM 201 21 NM4 1020 277 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 308: ...308 JOHNSON CONTROLS FORM 201 21 NM4 1020 308 JOHNSON CONTROLS MAINTENANCE NOTES ...
Страница 309: ...309 JOHNSON CONTROLS FORM 201 21 NM4 1020 309 JOHNSON CONTROLS 9 NOTES ...