170
JOHNSON CONTROLS
Turn on a Fan Stage
Every 5 sec
285
PSIG
Turn on a Fan Stage
every 15 min
250
PSIG
Discharge Pressure 150 – 250 PSIG
150
PSIG
Turn off Fan Stage
every 15 min.
120
PSIG
Turn off a Fan Stage
every 5 sec.
0 PSIG
Note:
A low Oil - Suction differential Pressure less than 75 PSID
will cause the micro to turn a fan stage Off every 5 sec. This
will override pressure control of the fans.
EPROM Version C.A14.09.03 (A85F),
other .03 versions and higher
Fan operation is outlined in Table 6. Condenser fan ON
conditions are governed solely by the Discharge Pressure
(DP). When the DP rises above 205 PSIG, fan stage 1 is
activated. From there, subsequent fan stages are activated
as the discharge pressure rises. The system will remain at
the highest fan stage reached unless the OFF conditions
outlined in the next paragraph are satisfied.
Condenser fan OFF conditions are governed by both the DP
and OAT. Fan staging will be decreased from the highest
fan stage reached if both the DP and OAT requirements
are met. For example, if a system is at fan stage 3, and the
DP falls below 195 PSIG and the OAT drops below 75°
F, the fan stage will be reduced to stage 3.
TABLE 5 –
CONDENSER FAN CONTROL
(EPROM VERSIONS C.A32.09.02 (0483),
C.ACS.09.02 (D87E), AND C.A06.09.03
(EIOC)
Fan
ON *
OFF *
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output*
1
1
>205 PSIG
<135 PSIG & <60°F
9M
130
15
SYS1
2
3
>265 PSIG
<160 PSIG & <65°F
10M
131
14
3
5
>285 PSIG
<180 PSIG & <70°F
11M
132
10
4
1, 5
>205 PSIG
<135 PSIG & <75°F
9M, 11M
130, 132
10,15
SYS2
5
3, 5
>265 PSIG
<160 PSIG & <80°F
10M, 11M
131, 132
10, 14
6
1, 3, 5
>285 PSIG
<180 PSIG & <85°F
9M, 10M, 11M
130, 131, 132
10, 14, 15
TABLE 6 –
CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 3 FANS/SYSTEM (EPROM VERSIONS C.A14.09.03 (A85F), OTHER .03 VERSIONS, AND
HIGHER
* Sys 1 Outputs are on Relay Board #1
Sys 2 Outputs are on Relay Output Board #2
Micro Panel Contents
Содержание YCAS0098EB
Страница 36: ...36 JOHNSON CONTROLS POWER AND CONTROL PANEL LAYOUTS WYE DELTA TYPICAL FIG 8 POWER PANEL SECTION 00263VIP 4...
Страница 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Страница 64: ...64 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 18 ELEMENTARY DIAGRAM ACROSS THE LINE START...
Страница 68: ...68 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 21 ELEMENTARY DIAGRAM WYE DELTA START...
Страница 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Страница 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Страница 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Страница 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Страница 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Страница 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Страница 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Страница 113: ...113 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR COMPONENTS CONT D FIG 40 COMPRESSOR COMPONENTS LD03669 7...
Страница 114: ...114 JOHNSON CONTROLS COMPRESSOR COMPONENTS CONT D FIG 41 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Страница 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Страница 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...