the code is being keyed in, the digits are not displayed
but are shown as “*” as shown:
When the Enter key is pressed, the following message
will appear:
Key in a “1” for if default setpoints are required, or a “0”
for individually programmed values, then press Enter to
store the selection into memory.
If individual programming is selected, the display will
now return to the Status display. If a default setpoints
have been selected, the display will momentarily dis-
play the message shown below before returning to the
Status display:
It is often easier to select Default
Setpoints and then reprogram a few
that require changing rather than
programming each individual value
from scratch.
A list of the default values entered into memory, if this
program option is selected, is shown below:
8.3
PROGRAMMING “DEFAULT” VALUES
Programmable values may be individually programmed at
start-up or any time thereafter. For ease of programming,
once the type of refrigerant is programmed in under the
Program key, a “defaults password” may be programmed
to automatically program default values into memory.
This will preset all programmable values under the
Program key to values that will allow operation of the
chiller under most operating conditions. This allows
quick start-up programming for typical chilled water
applications.
To program the default values into memory, first press
the PROGRAM key followed by the ENTER key, to
program the “refrigerant type.” Press the Program key
again, key in the numbers “6140”, then press Enter. As
P R O G R A M M O D E
* * * *
D E F A U L T S E T P O I N T S ?
1 = Y E S , 0 = N O, 1
P R O G R A M O P T I O N S S E T
T O D E F A U L T V A L U E S
If manual control is desired, press the
or
key. One
of the following messages will be displayed:
System 1, 2, 3 or 4 can be selected as the lead by pressing
the
or
key. The ENTER key must be pressed to
save the selection in memory.
Automatic/Manual Power Failure Restart
The chiller may be selected for “Automatic” or “Man-
ual” restart after a power failure. In most instances,
“Automatic Restart” is preferred to allow the chiller to
automatically restart when power is reapplied after a
power failure. When “Manual” is selected, the chiller
will not operate after re-application of power until the
ON / OFF Rocker Switch on the keypad is cycled OFF
and then ON.
In most applications, it is undesirable
to use Manual Reset on power failure
since chillers normally are required
to auto‑restart after a power failure.
L E A D / L A G C O N T R O L
M A N U A L S Y S 2 L E A D
L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
P O W E R F A I L R E S T A R T
A U T O
M
A T I C
6140
Programmable Value
Default
Setting
Discharge Pressure Cutout
R22 399 PSIG (28 Bar)
Low Ambient Cutout
Std. Amb.
25°F (-4°F)
Low Amb.
25°F (-4°F)
High Ambient Temperature Cutout
130°F (38°C)
Discharge Pressure Unload
R22 375 PSIG (26
Bar)
High Motor Current Unload
100%
Anti-Recycle Timer
600 sec.
Leaving Chilled Liquid Temp Cutout
36°F (2°C)
Suction Pressure Cutout
R22 44 PSIG (3 Bar)
Micro Panel Contents
Содержание YCAS0098EB
Страница 36: ...36 JOHNSON CONTROLS POWER AND CONTROL PANEL LAYOUTS WYE DELTA TYPICAL FIG 8 POWER PANEL SECTION 00263VIP 4...
Страница 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Страница 64: ...64 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 18 ELEMENTARY DIAGRAM ACROSS THE LINE START...
Страница 68: ...68 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 21 ELEMENTARY DIAGRAM WYE DELTA START...
Страница 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Страница 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Страница 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Страница 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Страница 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Страница 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Страница 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Страница 113: ...113 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR COMPONENTS CONT D FIG 40 COMPRESSOR COMPONENTS LD03669 7...
Страница 114: ...114 JOHNSON CONTROLS COMPRESSOR COMPONENTS CONT D FIG 41 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Страница 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Страница 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...