FORM 160.54-M1(503)
93
YORK INTERNATIONAL
FIG. 51 –
REFRIGERANT LIQUID LEVEL SENSOR
LD04091
14
less than the Setpoint, the rate in
fl
uence is de ter mined by
how close the result is to the Setpoint; close yields larg er
in
fl
uence, further yields small er in
fl
u ence.
Therefore, per the above, the values programmed for Pro-
portion Limit Open/Close and Rate Limit Open/Close de-
termine the sensitivity of the level control. Smaller val ues
generally yield greater response for the same level change
in the Level control Period. Also, the small er the value
programmed for the Level Con trol Period, the more often
an output signal is applied to the Variable Ori
fi
ce Actua-
tor. With Flash memory Card version C.MLM.01.06.xxx
and later or C.MLM.04.02.xxx, the duration of the open
and close pulse applied to the Valve Actuator is in de -
pen dent of the selected Period Setpoint. It is a
fi
xed per-
centage of 3.5 seconds. Previously, it was a per cent age
of the Period Setpoint. Therefore, longer Pe ri ods would
pro duce longer output pulses for the same error, resulting
in unstable operation under certain con di tions.
The ori
fi
ce valve movement is animated on the Re frig er ant
Level Control Screen as follows: when 0-20% open, shown
fully closed; 20 - 40% open, shown as 20% open; 40 - 60%
open, shown as 40% open; 60 - 80% open, shown as 80%
open; 80 - 100% open, shown as 100% open.
MANUAL OPERATION
The Ori
fi
ce Actuator can be manually controlled from the
Keypad using the Refrigerant Level Control Screen after
logging in at
SERVIC
E access level. Open, Close, Hold
and Auto keys are used to control the Variable Or i
fi
ce.
Using the Open, Close and Hold keys, the Vari able Ori-
fi
ce can be placed in a
fi
xed position. Pressing the Auto
key returns Level Control to Automatic op er a tion.
ACTUATORS
New production units use a Belimo actuator that op er ates
from 24VAC. If the OptiView Control Center is retro
fi
t
to an existing chiller, the chiller could be equipped with
a Bar ber-Coleman actuator that op er ates from 115VAC.
The interface for both actuators is shown in Fig. 52. The
description of the operation of both ac tu a tors is in the
“I/O Board” section of this book.
Содержание MAXE OPTIVIEW YK
Страница 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Страница 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Страница 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Страница 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Страница 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...