Service Information Letters / Bulletins
Proximity Probe/Limit Switch
Previously, YK chillers equipped with “P” compressors used the High Speed Thrust Bearing Limit Switch and all
other compressors used the Proximity Probe. With Style “F” chillers, only the “J” compressor will use the Prox-
imity Probe. Compressors “G”, “H” and “P” will use the Limit Switch.
In previous Flash memory card versions, the Thrust Bearing Limit Switch indication shows a lit LED for a normal
condition and unlit for a faulted condition. In this version, an unlit LED indicates a normal condition and a lit
LED indicates a faulted condition.
Refrigerant Level Control
In previous Flash Memory Card versions, this control operates as follows:
When the chiller enters
“System Run”
, if the Refrigerant Level Position is less than the
CONTROL
SETPOINT,
a linearly increasing ramp limit, called the
REFRIGERANT LEVEL TARGET
, is applied to the
CONTROL SETPOINT
. This ramp limit allows the level to go from the present programmed level to the pro-
grammed
CONTROL SETPOINT
over a period of 15 minutes. During these 15 minutes, the
REFRIGERANT
LEVEL TARGET
is used to control the condenser refrigerant level. The Control
SETPOINT
is then used to
control the refrigerant level for the remainder of chiller run.
In this version, the control will operate as follows:
•
While the chiller is stopped, or if the Level Control is disabled, the Refrigerant level
“Lower”
output is
energized.
•
Upon entering chiller Prelube, the Refrigerant Level
“Raise”
output is energized for the length of the pro-
grammable
VALVE PRESET TIME
setpoint (0 to 100 seconds; default 50; Service access level). After
pre-positioning, the valve is held in this position until the
fi
rst 3 minutes of chiller run time have elapsed.
Setting the
VALVE PRESET TIME
to 0 seconds disables this pre-positioning feature. Setting the Valve
Preset Time to a value greater than 50 seconds has no effect on the Prelube time.
•
After 3 minutes of run time, if the Refrigerant Level is less than the
CONTROL
Setpoint, a linearly in-
creasing ramp limit, called the
REFRIGERANT LEVEL TARGET
, is applied to the programmed Con-
trol Setpoint. This ramp limit allows the level to go from the present level to the
CONTROL SETPOINT
over a period of time programmed as the
RAMP-UP TIME
Setpoint (3 to 15 minutes; default 8; Service
access level). During this ramp-up period, the
REFRIGERANT LEVEL TARGET
is used to control
the refrigerant level in the condenser. The CONTROL SETPOINT is used to control the level during the
remainder of chiller run.
•
If the
VALVE PRESET TIME SETPOINT
is set to 0 seconds and the
RAMP-UP TIME
Setpoint is set
to 15 minutes, Refrigerant Level Control will operate exactly the same as previous Flash Memory Card
versions.
Microboards
Since the new version Flash Memory Card (as described above) is applicable to all YK chillers with any compres-
sor, the Microboard replacement kit 331-01730-604 previously supplied for YK chillers equipped with “P” com-
pressors is no longer required. The standard 331-01730-601 Microboard replacement kit will be supplied when
the 331-01730-604 is ordered.
SI0034 (203) - SOFTWARE ENHANCEMENTS EFFECTIVE AUGUST 2002 (CONT'D)
Содержание MAXE OPTIVIEW YK
Страница 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Страница 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Страница 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Страница 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Страница 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...