EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(120) Ambient Temperature Restriction Setpoint Compensation (for Auxiliary Heater Setting) (q5)
This function is utilized to change the outdoor ambient temperature condition to change operation from
auxiliary heater only to Thermo-ON with auxiliary heater.
This function is invalid when the function of "Auxiliary Heater Setting" is invalid.
Setting Condition
Actual Control Temperature
00 (Standard)
(q4) + 4
o
F (2.5
o
C)
01
(q4) + 5
o
F (3.0
o
C)
02
(q4) + 6
o
F (3.5
o
C)
03
(q4) + 1
o
F (0.5
o
C)
04
(q4) + 2
o
F (1.0
o
C)
05
(q4) + 3
o
F (1.5
o
C)
06
(q4) + 3
o
F (2.0
o
C)
(121) Not Prepared (q6)
(122) Not Prepared (q7)
(123) Not Prepared (q8)
(124) Not Prepared (q9)
(125) Not Prepared (qA)
(126) Not Prepared (qb)
(127) Not Prepared (qC)
(128) Not Prepared (qd)
(129) Dual Setpoint (for Automatic COOL/HEAT Operation) (r1)
This function is utilized to activate/deactivate dual setpoint of cooling and heating in automatic cooling
and heating operation.
This function is invalid when the function of "Automatic COOL/HEAT Operation" is invalid.
(130) Cooling/Heating Changeover Temperature (for Automatic COOL/HEAT Operation) (r2)
This function is utilized to change the indoor temperature condition to Thermo-ON/OFF.
This function is invalid when the function of "Dual Setpoint" is invalid.
In case dual setpoint is selected in automatic heating/cooling operation, during auto mode both cooling
setpoint and heating setpoint can be selected.
By default, temperature when the heating/cooling mode changes are as follows.
Cooling mode changes to heating mode when the indoor temperature is heating setpoint -2
o
F (-1
o
C).
Heating mode changes to cooling mode when the indoor temperature is cooling se2
o
F (+1
o
C).
Setting Condition
Actual Control Temperature
00 (Standard)
2
o
F (1.0
o
C)
01
3
o
F (1.5
o
C)
02
3
o
F (2.0
o
C)
03
4
o
F (2.5
o
C)
04
5
o
F (3.0
o
C)
05
1
o
F (0.5
o
C)
NOTE:
Be sure to use only the "00" setting condition when combining this "q5" function with a water source
unit.
Содержание HIDS006B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...