6-8
SM-18001-rev.1
FIELD WORK INSTRUCTIONS
6.6 Service and Maintenance Record
Service and Maintenance Record
No.
Check Item
Action
Judgment
1
Is service space sufficient?
YES or NO
2
Short Circuit of Discharged Air?
YES or NO
3
Any Heat Influence?
YES or NO
4
Is ground wiring connected?
YES or NO
5
Refrigeration Piping
GOOD or NOT GOOD
6
Fixing of Units
GOOD or NOT GOOD
7
Any Damage on External or Internal
Surface?
YES or NO
8
Checking of Screws and Bolts
Tighten them if they are loosened.
TIGHTENED or
NOT TIGHTENED
9
Tightening of Terminal Screws
Tighten all terminal screws with a
Phillips screwdriver.
TIGHTENED or
NOT TIGHTENED
10
Are compressor terminals
tightly fixed?
Check all compressor terminals are
tightly fixed.
GOOD or NOT GOOD
11 Insulation Resistance
Measure insulation resistance with
insulation resistance-meter.
Comp. and Fan
Motor: greater than 3M
W
Others: greater than 3M
W
GOOD or NOT GOOD
12
Does condensate water smoothly flow?
Check for smooth flow by
pouring water.
GOOD or NOT GOOD
13
Check for leakage at compressor.
Check for any leakage.
GOOD or NOT GOOD
14
Check for leakage at
outdoor heat exchanger.
Check for any leakage.
GOOD or NOT GOOD
15 Check for leakage at
indoor heat exchanger.
Check for any leakage.
GOOD or NOT GOOD
16
Check for leakage at reversing valve.
Check for any leakage.
GOOD or NOT GOOD
17
Check for leakage at check valve.
Check for any leakage.
GOOD or NOT GOOD
18
Check for leakage at accumulator.
Check for any leakage.
GOOD or NOT GOOD
19
Check for leakage at strainer.
Check for any leakage.
GOOD or NOT GOOD
20
Check for leakage at
electronic expansion valve.
Check for any leakage.
GOOD or NOT GOOD
21
Check for leakage at piping.
Check for any leakage.
GOOD or NOT GOOD
22
Check direction of fans.
by Viewing or Airflow Volume
GOOD or NOT GOOD
23
Voltage among each phase.
Check the voltage is within
the specified range.
GOOD or NOT GOOD
24
Vibration and Sound
Check fan, compressor, piping.
GOOD or NOT GOOD
25 Activation of Each Operation Mode
Check activation of COOL,
HEAT, STOP and TEMP. switches.
GOOD or NOT GOOD
26
High Pressure Cut-out Switch
Check actual activation value.
GOOD or NOT GOOD
27
Check activation of drain-up mechanism.
Check it during cooling operation.
GOOD or NOT GOOD
28
Indoor Inlet Air Temp. (DB/WB)
o
F DB/
o
F WB
29
Indoor Outlet Air Temp. (DB/WB)
o
F DB/
o
F WB
30
Outdoor Inlet Air Temp. (DB/WB)
o
F DB/
o
F WB
31
Outdoor Outlet Air Temp. (DB/WB)
o
F DB/
o
F WB
32
High Pressure Sensor
psi(G)
33
Low Pressure Sensor
psi(G)
34
Operating Voltage
V
35 Operating Current
A
36
Instruction for Cleaning of Air Filter to Client
DONE or NOT YET
37 Instruction for Cleaning Method to Client
DONE or NOT YET
38
Instruction for Operation to Client
DONE or NOT YET
Содержание HIDS006B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...