SM-18001-rev.1
5-19
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
53
F1
Automatic OFF Timer Setting
* Do not set the functions “0C”~“0F”
when 2 (two) wired controllers are
used in the same controller group
×
00
01
02
•
•
23
24
0A
0B
0C
0D
0E
0F
No Function
OFF Timer by 1 hr
OFF Timer by 2 hrs
•
•
OFF Timer by 23 hrs
OFF Timer by 24 hrs
OFF Timer by 30 min.
OFF Timer by 90 min.
OFF Timer by 40 min.
OFF Timer by 45 min.
OFF Timer by 50 min.
OFF Timer by 55 min.
}
Do not set them when
two wired controllers
are used.
54
F2
Wired Controller Main-Sub Setting
×
00
01
Main
Sub
55
F3
Automatic Reset of Setting
Temperature (*2)
×
00
01
Not Available
Available
56
F4
Automatic Reset Time
×
00
01
02
03
30 min. (Factory-Setting)
15 min.
60 min.
90 min.
57
F5
Automatic Reset Temperature
for Cooling
×
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C) (Factory-Setting)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
58
F6
Automatic Reset Temperature
for Heating
×
62 (17)
64 (18)
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
62
o
F (17
o
C)
64
o
F (18
o
C)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C) (Factory-Setting)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
59
F7
Operation Stoppage Prevention by
Wired Controller Operational Error
(*5)
×
00
01
Not Available
Available
60
F8
Lock Function for Operation Mode
Selection
×
00
01
Not Available
Available (Factory-Setting)
61
F9
Lock Function for Temperature
Setting
×
00
01
Not Available
Available (Factory-Setting)
62
FA
Lock Function for Fan Speed
Selection
×
00
01
Not Available
Available (Factory-Setting)
63
Fb Lock Function for Swing Louver
Operation
×
00
01
Not Available
Available (Factory-Setting)
Содержание HIDS006B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...