SM-18001-rev.1
3-45
TROUBLESHOOTING
Event
Cause
Check Item
Action
(Turn OFF Main Switch
)
“Motion Sensor
is activated” is
indicated on Wired
Controller LCD.
Reaction rate is always
100%.
Check the “Check Mode 1:
q1” on the wired controller.
↓
Check if there is motion
sensor with “Reaction rate
always 100%”.
True: Replace motion
and radiation sensors
PCB.
False: Replace control
PCB.
Operation Stops
though Someone is
Present.
Reaction rate is always
0%.
Operate under detection
area of motion sensor and
check the “Check Mode 1:
q1” on the wired controller.
↓
Check if there are motion
sensors with “Reaction
rate always 0%”.
True: Replace motion
and radiation sensors
PCB.
Not Operating
in “Avoid Air” or
“Receive” though
Someone is
Present.
False: Sensitivity may
be low. Adjust the
[Optional Function: K6]
to [01: High Sensitivity]
and see if there are any
changes. If the symptom
continues, replace
motion and radiation
sensors PCB.
Operation Continues
though No One is
Present.
Motion sensor setting
is disabled on the wired
controller.
Check setting on the wired
controller.
Correct the setting.
Motion sensor setting
of No presence is set to
other than “Stop” on the
wired controller.
Check setting on the wired
controller.
Correct the setting.
There are heat source
other than human in the
detecting area of the
sensor.
Check heat source
(a moving object whose
temperature is different
from surroundings).
Remove it.
There is sensor with high
sensitivity.
Stop the operation from the
wired controller, no motion
in the detection area of the
motion sensor and check
the “Check Mode 1: q1”.
↓
Check if there is no motion
sensor with “Reaction rate
0%”.
True: Replace motion
and radiation sensors
PCB.
False: No problem.
Adjust the [Optional
Function: K6] to [02: Low
Sensitivity] and see if
there are any changes. If
the symptom continues,
replace motion and
radiation sensors PCB.
Operating in “Avoid Air” or “Receive”.
Operating in “Avoid
Air” or “Receive”
though No One is
Present.
15 minutes has not
passed since someone
left the room.
Check the louver operation
after no one has been in
the room for more than 15
minutes.
Not operating in “Avoid
Air” or “Receive”. This is
normal operation.
There are heat sources
other than human in the
detection area of the
sensor.
Check heat source
(a moving object whose
temperature is different
from surroundings).
Remove it.
“Radiation Sensor is
activated” is indicated
on Wired Controller
LCD.
Radiation sensor element
is abnormal.
Replace motion and
radiation sensors PCB.
Abnormalities of Devices
(Motion and Radiation Sensor)
Other
Abnormalities
Содержание HIDS006B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...