SM-18001-rev.1
5-25
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(7) Fixing of Operation as Exclusive Cooling Unit (b7)
This function is utilized when exclusive cooling operation is required.
This function invalidates the heating operation and the automatic COOL/HEAT operation, as the
operation of exclusive cooling unit.
(8) Automatic COOL/HEAT Operation (b8)
This function is utilized to change cooling and heating operation automatically (the same operation
mode for indoor units in the same refrigerant cycle).
This function is invalid when the outdoor unit is cooling-only model or the function of “Fixing of
Operation as Exclusive Cooling Unit” is valid.
(9) Fixing of Fan Speed (b9)
This function is utilized to fix the fan speed.
When this function is valid, the fan speed can not be changed by the wired controller.
(10) Not Prepared (bA)
(11) Cooling Temperature Compensation due to Uneven Heat Load (bb)
This function is utilized to provide the longer cooling operation time than the standard.
When this function is valid, Thermo-ON/OFF is controlled under the lower temperature conditions than
the setting temperature (the indicated value) of the wired controller.
(12) Not Prepared (bC)
(13) Not Prepared (bd)
(14) Not Prepared (bE)
(15) Not Prepared (C1)
(16) Not Prepared (C2)
(17) Not Prepared (C3)
(18) Not Prepared (C4)
(19) Hi Speed (Except for Hi Speed during Heating Thermo-OFF) (C5)
This function is utilized to increase the fan speed for the sufficient air flow volume. It is recommended
to use when the air flow volume is decreased by using the optional high ceiling installation or etc.
(20) Hi Speed during Heating Thermo-OFF (C6)
This function is utilized to increase the fan speed during heating Thermo-OFF with the function (19).
(The fan speed does not increase during heating Thermo-OFF even if the function (19) is valid.)
(21) Canceling of Enforced 3 Minutes Minimum Operation Time of Compressor (C7)
The compressor operation is enabled for a minimum of 3 minutes when operation is started by the
"Enforce 3 Minutes Minimum Operation Time of Compressor". This function is utilized to cancel
the function “Enforced 3 Minutes Minimum Operation Time of Compressor” (Enforced 3 Minutes
Compressor Guard).
NOTE:
The compressor operation is stopped immediately as following conditions.
● The protection device is activated.
● The operation stop button is pressed.
Setting Temperature for Room Temperature Control during Cooling
Setting Condition
Actual Control Temperature
00 (Standard)
Wired Controller Setting Temperature (Indicated Value)
01
Wired Controller Setting Temperature (Indicated Value) -2
o
F (-1
o
C)
02
Wired Controller Setting Temperature (Indicated Value) -3
o
F (-2
o
C)
NOTE:
The minimum setting temperature after correction is 66
o
F (19
o
C).
Содержание HIDS006B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...