JOHNSON CONTROLS
87
SECTION 5 - COMMISSIONING
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
5
JOHNSON CONTROLS
6
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
cOMBUSTION DATA
MEASURED BY
SPEcIFI-
cATION
STAN-
DARD
LOw
MIDDLE
hIGh
OUTPUT VALUE
%
Control panel
FUEL DAMPER POSITION
%
Damper pointer
AIR DAMPER POSITION
%
Damper pointer
FUEL PRIMARY PRESSURE
(P1)
Pressure gauge
FUEL SEcONDARY PRES-
SURE (P2)
Pressure gauge
FUEL cONSUMPTION (SEE
NOTES)
m
3
/h
Flow meter
FUEL cONSUMPTION (SEE
NOTES)
m
3
N/h
Calculation or flow
meter
ExhAUST GAS O
2
cON-
cENTRATION
%
Exhaust gas analyzer
4.0~8.0
ExhAUST GAS cO cON-
cENTRATION
ppm
Exhaust gas analyzer
≤100
ExhAUST GAS cO
2
cON-
cENTRATION
%
Exhaust gas analyzer
wIND BOx PRESSURE
Water manometer
DRAFT PRESSURE (P3)
Water manometer
0~-49 kPa
FURNAcE PRESSURE (P4)
Water manometer
FLAME cURRENT
μA
Flame current meter
≥2.0
BURNER FAN OPERATION
cURRENT
A
Cramp meter
ExhAUST GAS TEMPERA-
TURE
°C
Control panel
≤250
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (2/3)
NOTES:
If gas flow rate is taken as m
3
/h, calculate m
3
N/h with fuel pressure and ambient temperature.
LD20247
P1
P2
Air
P3
P4
Gas
Ambient temperature: °C