SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
LD18119
FIGURE 3 -
WARNING
Rigging and lifting should only be done by
a professional rigger in accordance with a
written rigging and lifting plan. The most
appropriate rigging and lifting method
will depend on job specific factors, such
as the rigging equipment available and
site needs. Therefore, a professional rig-
ger must determine the rigging and lifting
method to be used, and it is beyond the
scope of this manual to specify rigging and
lifting details.
This chiller-heater is for air conditioning or a cooling
manufacturing process. Transport, store, and use this
chiller-heater under the following conditions:
Installation location: Indoor, non-explosion area
Ambient temperature: 10 ~ 40°C
Humidity:
10 ~ 90% (RH%)
Altitude:
1000 m or lower
If the plant room will ever get below 10°C, you must
have the cold ambient option.