Operation instructions of wire controller
33
(3)--Air-conditioning temperature and tank temperature display area as well as the set value
display area
(4)--Number of display code
(5)--Operation mode display area
(6)--Status display areas such as screen lock, communication, etc.
(7)--Key area
4.2 Power-on initialization
Entry conditions: power up
Exit condition:
1
)
Exit it after 1 unit is searched
2
)
If the unit cannot be searched, wait for 60 seconds and then report the
communication Fault
Execute:
1)
Turn off the buzzer after it is turned on for 100 mS
2)
Turn the backlight off within 40 seconds after it is turned on
3)
Shield the operation of the wire controller
4) Read the setting value of the dial switch and handle with it (refer to the setting
for the dial switch)
5)
Read the stored value and process it
6)
Find the unit
If the unit is found out, exit the initialization.
4.3 Restore the Default Value
At the daily display state, press and hold
for 5 seconds to enter the parameter setting
state for the system level; firstly enter the setting item 01, which is the item of restoring the default
value; at the same time, display the character of 01 at the display area of temperature; flash the
current parameter value at the display area of time; 00 means not restoring the default value, and
01 means confirming the default value; If you want to restore the default value, set the display
area of time to 01; then press the key
to confirm the current operation, or press the key
to exit the parameter setting, or automatically exit the state if there is no operation in 10s.
4.4 Displaystatus
4.4.1 Initialization state
1)
Display of wire-controller lock: the wire controller is in the locked state and the control
operation cannot be performed, with the display of icon
2)
Display of keypad lock: the key is in locked state, and the control operation cannot be carried
out, with the display of icon