Introduction of Unit
7
1.4.
Operating Range
Voltage Range
Standard of Power Supply: 380VAC-3N-50Hz
Maximum allowable fluctuation range of the power supply voltage shall be ±10%
Unbalance rate of the three-phase voltage shall be less than 2%
Temperature Range
Items
Range
Usage environment for 7-inch screen controller
-20 - 60°C
; RH≤95%; Non
condensing
Usage environment for wire controller
0-50°C, RH-95%; Noncondensing
Temperature range of unit’s operating environment
-10°C -48°C
Operation of Cooling
Using-side water inflow 10°C (-5°C*) - 30°C
Using-side water outflow 5°C (-10°C*) - 24°C
Heat-source-side water inflow 15°C - 50°C
Operation of Heating
Using-side water inflow 15°C - 50°C
Using-side water outflow 20°C - 55°C
Heat-source-side water inflow 10°C - 30°C
Operation of Heat Recovery
Using-side water inflow 10°C - 30°C
Using-side water outflow 5°C - 24°C
Returning hot water 30°C - 50°C
Note:
Returning water temperature control is set as default and recommended
The above data is obtained in the laboratory. In actual use, it will be biased by the influence factors, such as
installation location, etc.
* Saline-water Mode (for ethylene glycol aqueous solution only), and the set value shall be selected in
accordance with ethylene glycol’s concentration
Water temperature’s operating range diagram for standard unit is as follows
Note: The above diagram is standard unit operating range diagram. For the operation range of saline-water mode,
please consult Johnson Controls
Other Requirements: