<5. Wiring>
5-3
IM 11M13A01-04E
5.1.2 Wiring
Make the following wiring for the equipment. It requires a maximum of four wiring connections as
shown below.
(1) Analog output signal
(2) Power and ground
(3) Contact output
(4) Contact input
1
DI-1
2
DI-2
3
DI-C
4
DO-1
5
DO-1
6
DO-2
7
DO-2
8
FG
9
AO
(+)
10
AO
(-)
11
L
12
N
13
G
14
FG
F5-2E.ai
Contact input 1
Contact output 2
Contact output 1
Analog output
4-20 mA DC
100 to 240 V AC,
50 or 60 Hz
Digital output
Contact input 2
The protective grounding for the analyzer shall be connected either the protective ground terminal in the equipment
or the ground terminal on the case. Standard regarding grounding: Ground to earth, ground resistance: 100 Ω or less.
Figure 5.2
Wiring Connection
5.1.3 Mounting of Cable Gland
For each wiring inlet connection of the equipment, mount the conduit appropriate for the screw size or
a cable gland.
25
F5-3E.ai
Cable gland
Rc1/4 or 1/4NPT
(Reference gas inlet)
Rc1/4 or 1/4NPT
(Calibration gas inlet)
M20 x1.5, 1/2 NPT or the like
(Wiring connection)
Unit: mm
Figure 5.3
Cable Gland Mounting