<8. Maintenance>
8-10
IM 01C50E01-01EN
Integral
indicator
Factory
NAMUR
category
Bit
Diagnostic
Status
Diagnostic
Status Detail
Cause
Release/
recovery
conditions
(except
restart)
Output
Operation
Action
AL.50
S1.SPAN
C
Bit
25
Faults in
sensor or
actuator
element
SENSOR1
SPAN ADJ
ERR
Sensor 1 input
adjustment range
error
Recovers
when the
input is within
the range.
Normal action
Check
the input
adjustment
setting.
AL.51
S1.ZERO
SENSOR1
ZERO ADJ
ERR
Sensor 1 input
adjustment value
error
Recovers
when the
input value
is a normal
value.
Normal action
Check
the input
adjustment
setting.
AL.52
S2.SPAN
*4
SENSOR2
SPAN ADJ
ERR
Sensor 2 input
adjustment range
error
Recovers
when the
input is within
the range.
Normal action
Check
the input
adjustment
setting.
AL.53
S2.ZERO
*4
SENSOR2
ZERO ADJ
ERR
Sensor 2 input
adjustment value
error
Recovers
when the
input value
is a normal
value.
Normal action
Check
the input
adjustment
setting.
AL.60
AI1.OS
Bit
24
Out of service
AI1 O/S
MODE
AI1 block is O/S
mode.
Recovers
when the
mode target
of AI1 block
is other than
O/S.
Hold
Check the
AI1 block
setting.
AL.61
AI2.OS
*4
AI2 O/S
MODE
AI2 block is O/S
mode.
Recovers
when the
mode target
of AI1 block
is other than
O/S.
Hold
Check the
AI2 block
setting.
AL.64
AI1.SIM
Bit
17
Simulation is
active
AI1
SIMULATE
MODE
Simulate Switch
of the AI1 block is
enabled
Recovers
when the
Simulate
Switch of AI1
block is set
to DISABLE.
Normal action
Check the
AI1 block
setting.
AL.65
AI2.SIM
*4
AI2
SIMULATE
MODE
Simulate Switch
of the AI2 block is
enabled
Recovers
when the
Simulate
Switch of AI2
block is set
to DISABLE.
Normal action
Check the
AI2 block
setting.
*1: “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
*2: When the device detects “AL02 AMP.ERR,” “AL03 FUP.ERR,” “AL10 S1.FAIL,” “AL11 S2.FAIL,” and “AL12 RJ.FAIL”, the LCD
display stays on regardless of the status in LCD mode.
*3:
When the ambient temperature is higher than 60°C, AL.70 may be generated despite the indication of Energy Left shows sufficiently
remained. However, it does not affect the device operation. This is caused by the change of battery inner status with extremely
low power consumption under high temperature environment. It is recommended to set the data updating period to 15 seconds or
shorter.
*4:
Applicable for dual sensor input.