![YOKOGAWA YTA510 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/yokogawa/yta510/yta510_user-manual_3838199033.webp)
<6. Operation>
6-4
IM 01C50E01-01EN
(a) Deep sleep
F0604.ai
(b) Ready and pause
F0605.ai
(c) Confirm connecting status
F0606.ai
(d) Join
F0607.ai
NOTE
If the transmitter searches the Field wireless
Network for long time ambient temperature
condition, sometimes error "AL.20 LOWBAT" is
displayed on the Integral Indicator. Even though
using new batteries, it can occur. It occurs
because of battery characteristics. After joining
to the Field Wireless Network, this error will be
cleared within one hour if battery has no failure.
6.5 Shutting Down the
Transmitter
When shut down the transmitter, remove the battery
pack or set the transmitter to deep sleep mode by
the device configuration tool.
NOTE
•
Refer to subsection 8.4.4 “Replacing the
Battery Pack” for the battery pack removing.
•
When storing the instrument with a battery
pack inserted, it is recommended to put the
instrument into deep sleep mode to conserve
battery power. For details on how to switch to
deep sleep mode, refer to subsection 7.3.14
“Switching to the Deep Sleep Mode."