<7. Setting Parameters>
7-12
IM 01C50E01-01EN
Input
Output
GAIN
F0705.ai
ZERO
Figure 7.3
Trim function images
IMPORTANT
Setting the sensor type automatically resets the
zero-gain adjustment value to the factory setting.
2) Clearing the Adjustment Value
The adjustment value set with input adjustment
can be cleared and reset to the factory setting.
■ Procedure to call up the adjustment value reset
parameter (Cal Point Clear)
AI1/AI2 block: Cal Point Clear
Set the Cal Point Clear parameter to Clear.
7.3.14 Switching to the Deep Sleep Mode
When the instrument will not be used for a long
time, switch the instrument to the deep sleep mode
to conserve battery power. To switch to deep sleep
mode, follow the procedure below.
■ Procedure to call up the switch-to-deep-sleep
parameter (Special Cmd)
TRANSDUCER block : Special Cmd
Set deep sleep mode (Standby) to the Special
Cmd parameter for the TRANSDUCER block.
To start from deep sleep mode, remove and
insert the battery pack.
CAUTION
After setting the deep sleep mode by infrared
device configuration tool, keep the infrared port
of device away from any other infrared signals.
NOTE
• This procedure to switch to deep sleep mode
can only be use for wireless communication.
• Transmitter becomes the stop state after
setting deep sleep mode and cannot reply
any request from Communication Tool.
• For this reason, there is the case that an
error is display on Communication Tool.
• To wake up from deep sleep mode, please
pull battery pack and wait more than 30
seconds before attaching battery pack.
7.3.15 Switching to the Silence Mode
This is a function to pause the instrument when
it cannot join the field wireless network after a
specified time has elapsed. This function is effective
in conserving battery power when, for example, the
installation of the field wireless integrated gateway
is delayed compared to that of field wireless
devices. The default value is 28800 seconds
(about 8 hours). Thereafter, a cycle of a one-hour
pause and six-minute search is repeated until the
instrument can join the field wireless network.
• Procedure to call up the switch-to-silence
parameter (Radio Silence)
UAPMO block : Radio Silence
Set 0 to 2
31
seconds for the Radio Silence
parameter of the UAPMO block. If 0 is set, the
Radio Silence parameter is invalid. To start from
the silence mode, either remove and insert the
battery pack, or use the configuration tool.