6-6
IM 01B08D02-02EN
Direct Input Specifications
Item
mV Input
Thermocouple Input
Optional code
/A01
/A02
Input signal
DC potential difference: −50 to
+150 mV
JIS, ANSI standards
Thermocouple types K, T, J, E, B, R,
and S
IEC and ANSI standards
Type N
Measuring range span
10 to 100 mV DC
10 to 63 mV (thermoelectric power
equivalent)
Measuring range zero
elevation
Within whichever is smaller, three
times the span or ±50 mV
Within whichever is smaller, three
times the span or ±25 mV
Measuring range
Changeable on Engineering Display
Input resistor
1 MΩ (3 kΩ at power failure)
External input resistor
500 Ω or less
Allowable input voltage
and current
−0.5 to 4 V DC
Input l linearization
Not provided
Provided
1 to 5 V output
conversion accuracy
rating
Within ±0.2% of span
Whichever is greater, ±0.2% of
span or input equivalent ±20 µV
Reference junction
compensation error
−
Within ±1°C (*1)
*1: Type B does not conduct reference junction temperature compensation.
For types other than type B, the value obtained by multiplying the noted value by the following
coefficient (K) applies if the measurement temperature is 0°C or less.
K = (thermoelectric power for 1°C near 0°C) / (thermoelectric power for 1°C at measurement
temperature)
Item
Resistance Temperature
Detector Input
Potentiometer Input
Optional code
/A03
/A04
Input signal
RTD
Pt100(IPTS-68: JIS'89),
JPt100(JIS'89),
Pt100(ITS-90: JIS'97),
Pt50(JIS'81),
three-wire type
Measurement current: 1 mA
Potentiometer three-wire type
Measuring range span
10 to 650°C (Pt 100)
10 to 500°C (JPt 100)
Total resistance: 100 to 2000 Ω
Span: 80 to 2000 Ω
Measuring range zero
elevation
Within five times the span
50% or less of total resistance
Measuring range
Changeable on Engineering Display
External input resistance
10 Ω or less per wire (*1)
10 Ω or less per wire
Input linearization
Provided
Not provided
1 to 5 V output
conversion accuracy
rating
Whichever is greater, ±0.2% of
span or ±0.2°C
Within ±0.2% of span
*1: The value shall be equal or less than the smaller value out of 10 Ω per wire or (measurement
temperature span) × 0.4 Ω.
Note: There is no difference between the latest and the previous temperature tables as far as
applying them to the YS1000.
- TC: Latest version; IEC60584-1: 2013/JIS C1602:2015
Previous version; IEC60584-1: 1995/JIS C1602:1995
- RTD Latest version; IEC60751- 2008/JIS C1604:2013
Previous version; IEC751- 1995/JIS C1604:1997
6.1 General Specifications