Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
66
Reset Menu (
reset
)
The
Reset
menu is used to reset the totals and maximum or minimum
reading (peak or valley) reached by the process; both may be reset at
the same time by selecting “reset high & low” (
rst HL
). If
total
is set to
no
, the tare value used to zero the display may be reset by selecting
“reset tare” (
rst tr
).
Control Menu (
Contrl
)
The
Control
menu is used to control the 4-20 mA analog output and the
relays manually, ignoring the input. Each relay and analog output can be
programmed independently for manual control. Selecting automatic
control sets all relays and analog output for automatic operation.
Setting Up the Password (
pass
)
The
Password
menu is used for programming three levels of security to
prevent unauthorized changes to the programmed parameter settings
and to program the non-resettable totalizer.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total manually