Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
36
Setting the Input Signal (
Input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or
voltage (
volt
) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
±
10 VDC signals.
Setting the Totalizer Features (
total
)
To simply not display the total, select alternative display parameters in
the display (
dsplay
) menu.
Enable or disable the totalizer features by selecting “
Yes
” or “
no
” after
the input type has been set up. If the totalizer features are disabled, all
the totalizer features and functions are hidden from the menus. Level
and process meter features and functions are added to the menus.
If disabling the
total
parameter by selecting
no
, please refer to the
YPP6000 manual available at www.yokogawa-usa.com for instructions
on setting up the meter parameters.
Notes: 1. The totalizer continues working in the background.
2. When selecting "no" for Total, the meter now functions as a
YPP6000 Process Meter. We strongly suggest that you download
and use the YPP6000 instruction manual from our website
(www.yokogawa-usa.com) while in this mode of operation.