Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
15
IMMUNITY
EN 61326-1:2006
Measurement, control, and laboratory equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity standard
RFI - Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency
Magnetic Field
3 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Note:
Testing was conducted on YPP6200 meters installed through the
covers of grounded metal enclosures with cable shields grounded at
the point of entry representing installations designed to optimize
EMC performance.
Declaration of Conformity available at www.yokogawa-usa.com
SAFETY INFORMATION
!
CAUTION
:
Read complete
instructions prior to
installation and operation
of the meter.
WARNING
:
Risk of
electric shock or
personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed only by
trained service personnel.