
Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
45
Setting the Relay Operation (
relay
)
This menu is used to set up the operation of the relays.
!
CAUTION!
During setup, the relays do not follow the input and they will
remain in the state found prior to entering the Relay menu.
1. Relay
assignment
a. Rate for low and high alarm
b. Total
c. Grand
total
d. Modbus input process variable
2. Relay
action
a. Automatic reset only (non-latching)
b. Aut manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
condition has cleared)
e. Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
3. Set and reset points
4. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
5. Time
delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input (ignore, on, off)