2-4
IM 707281-01E
2.2 Connecting the Output Signal Wire
When connecting the output signal wire to the clamp type terminal, loosen the screw
holding down the clamp, insert the output signal wire into the opening, and then tighten
the screw.
Recommended length of the stripped portion of the output signal wire: 7 mm
Thickness of the output signal wire (for twisted wire)
: 0.5 to 1.5 mm
2
Clamping screw
For WE7282
Use a BNC cable for the output signal. The BNC cable is connected to the output
terminal (isolated BNC) on the front panel of the module. There are four channels of
output terminals.
CAUTION
• Do not apply voltages that exceed the following values, as it may damage the
module.
Maximum common mode voltage:
±
42.4 VDC+ACpeak between the ground and
the L terminal
Maximum voltage between channels:
±
42.4 VDC+ACpeak between terminals of
different channels
Note
The maximum length of the cable that is connected to the output connectors of WE7281/WE7282
is 20 m. However, if the cable length exceeds 3 m, undesirable effects such as delay in the rise
time of the output waveform or distortion may occur.
OUTPUT
10V
CH1
CH2
CH3
CH4