IM 05P01D31-11EN  page 1/12

Contents

1.  Safety Precautions

2.  Model and Suffix Codes

3.  How to Install

4.  Hardware Specifications

5.  How to Connect Wires

6.  Terminal Wiring Diagrams

Introduction

Thank you for purchasing the UT35A/UT32A Digital Indicating Controller.

This operation guide describes the basic operations of the UT35A/UT32A. The guide 

should be provided to the end user of this product.

Be sure to read this operation guide before using the product in order to ensure 

correct operation.

For details of each function, refer to the electronic manual. Before using the product, 

refer to the table of Model and Suffix Codes to make sure that the delivered product 

is consistent with the model and suffix codes you ordered. Also make sure that the 

following items are included in the package.

• Digital Indicating Controller (the model you ordered)

 ..............................

x1

• Set of Brackets ........................................................................................

x1

• Unit Label (L4502VZ)

 ..............................................................................

x1

• Tag Label (L4502VE)

 ..............................................................................

x1

• Operation Guide (this document)

 ............................................................

x6 (A3 size)

  (Installation and Wiring, Initial Settings, Operations, and Parameters)

Target Readers

This guide is intended for the following personnel;

•  Engineers responsible for installation, wiring, and maintenance of the equipment.

•  Personnel responsible for normal daily operation of the equipment.

1.  Safety Precautions

The following symbol is used on the instrument. It indicates the possibility of injury 

to the user or damage to the instrument, and signifies that the user must refer to 

the user’s manual for special instructions. The same symbol is used in the user’s 

manual on pages that the user needs to refer to, together with the term “WARNING” 

or “CAUTION.”

WARNING 

Calls attention to actions or conditions that could cause serious 

or fatal injury to the user, and indicates precautions that should be 

taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to 

the user or damage to the instrument or property and indicates pre-

cautions that should be taken to prevent such occurrences.

AC

AC/DC

 

The equipment wholly protected by double insulation or reinforced insulation.

  

Functional grounding terminals 

   

(Do not use this terminal as a protective grounding terminal).

Note

Identifies important information required to operate the instrument.

n

 Warning and Disclaimer

(1) YOKOGAWA makes no warranties regarding the product except those stated in 

the WARRANTY that is provided separately.

(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 

any person or entity for any loss or damage, direct or indirect, arising from the 

use of the product or from any unpredictable defect of the product.

n

 Safety, Protection, and Modification of the Product

(1) In order to protect the system controlled by this product and the product itself, 

and to ensure safe operation, observe the safety precautions described in the 

user’s manual. Use of the instrument in a manner not prescribed herein may 

compromise the product's functions and the protection features inherent in the 

device. We assume no liability for safety, or responsibility for the product's quality, 

performance or functionality should users fail to observe these instructions when 

operating the product.

(2) Installation  of  protection  and/or  safety  circuits  with  respect  to  a  lightning 

protector; protective equipment for the system controlled by the product and the 

product itself; foolproof or failsafe design of a process or line using the system 

controlled by the product or the product itself; and/or the design and installation 

of other protective and safety circuits are to be appropriately implemented as the 

customer deems necessary.

(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts 

or consumables.

(4) This product is not designed or manufactured to be used in critical applications 

that directly affect or threaten human lives. Such applications include nuclear 

power  equipment,  devices  using  radioactivity,  railway  facilities,  aviation 

equipment, air navigation facilities, aviation facilities, and medical equipment. 

If so used, it is the user’s responsibility to include in the system additional 

equipment and devices that ensure personnel safety.

(5) Modification of the product is strictly prohibited.

WARNING 

Power Supply

  Ensure that the instrument’s supply voltage matches the voltage 

of the power supply before turning ON the power.

l

  Do Not Use in an Explosive Atmosphere

  Do not operate the instrument in locations with combustible 

or explosive gases or steam. Operation in such environments 

constitutes an extreme safety hazard. Use of the instrument in 

environments with high concentrations of corrosive gas (H

2

S, 

SO

X

, etc.) for extended periods of time may cause a failure.

l

  Do Not Remove Internal Unit

  The internal unit should not be removed by anyone other than 

YOKOGAWA's service personnel. There are dangerous high 

voltage parts inside. Additionally, do not replace the fuse by 

yourself.

l

  Damage to the Protective Construction

  Operation of the instrument in a manner not specified in the 

user’s  manual may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-

ment this product may cause radio interference in which case the 

user needs to take adequate measures.

2.  Model and Suffix Codes

n

 UT35A 

[Style:S1]

Model

Suffix code

Optional 

suffix 

code

Description

UT35A

Digital Indicating Controller 

 

(provided with retransmission output or 15 V DC loop 

power supply, 2 DIs, and 3 DOs) 

 

(Power supply: 100-240 V AC)

Type 1: 

Basic 

control

-0

Standard type

-1

Position proportional type

-2

Heating/cooling type

Type 2: 

Functions

0

None

1

2 additional DIs, 2 additional DOs

2

5 additional DIs, 5 additional DOs

Type 3: Open 

networks

0

None

1

RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)

2

Ethernet communication (with serial gateway function)

3

CC-Link communication

4

PROFIBUS-DP communication

Display language (*1)

(Note)

-1

English

-2

German

-3

French

-4

Spanish

Case color (Note)

0

White (Light gray)

1

Black (Charcoal gray light)

Fixed code

-00

Always "-00"

Optional suffix codes

/LP

24 V DC loop power supply (*2)

/HA

Heater break alarm (*3)

/DC

Power supply 24 V AC/DC

/CT

Coating (*4)

*1: 

English, German, French, and Spanish can be displayed as the guide display.

*2: 

The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and 

Type 3 code (any of "0" or "1".) 

*3: 

The /HA option can be specified when the Type 1 code is “-0” or “-2”.

*4: 

When the /CT option is specified, the UT35A does not conform to the safety standards (UL 

and CSA) and CE marking.

Note: The last digit of the display language code (-x0) has been changed into the case color code.

n

 UT32A

[Style:S1]

Model

Suffix code

Optional 

suffix 

code

Description

UT32A

Digital Indicating Controller (provided with retrans-

mission output or 15 V DC loop power supply, 2 DIs, 

and 3 DOs) (Power supply: 100-240 V AC)

Type 1: 

Basic 

control

-0

Standard type

-1

Position proportional type

-2

Heating/cooling type

Type 2: 

Functions

0

None

1

RS-485 communication (Max. 38.4 kbps, 2-wire/4-

wire)

2

2 additional DIs and 2 additonal DOs

Type 3: 

Open networks

0

None

Display language (*1) 

(Note)

-1

English

-2

German

-3

French

-4

Spanish

Case color (Note)

0

White (Light gray)

1

Black (Charcoal gray light)

Fixed code

-00

Always "-00"

Optional suffix codes

/LP

24 V DC loop power supply (*2)

/HA

Heater break alarm (*3)

/DC

Power supply 24 V AC/DC

/CT

Coating (*4)

*1: 

English, German, French, and Spanish can be displayed as the guide display.

*2: 

The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1") 

and Type 2 code (any of "0" or "1.") Additionally, when the Type 2 code is "1", the RS-485 

communication is 2-wire system.

*3: 

The /HA option can be specified when the Type 1 code is "-0" or "-2."

*4: 

When the /CT option is specified, the UT32A does not conform to the safety standards (UL 

and CSA) and CE marking.

Note: The last digit of the display language code (-x0) has been changed into the case color code.

n

 Accessories (sold separately)

The following is an accessory sold separately.

•  LL50A Parameter Setting Software

Model

Suffix code

Description

LL50A

-00

Parameter Setting Software

•  Terminal Cover

  For UT35A: Model UTAP001; For UT32A: Model UTAP002

•  User’s Manual (A4 size)

 

Note: User’s Manual can be downloaded from a website.

• User’s Manual (CD-ROM), Model: UTAP003

 

Note: Contains all manuals.

3.  How to Install

n

 Installation Location

The  instrument  should  be  installed  in  indoor  locations  meeting  the  following 

conditions:

•  Instrumented panel

  This instrument is designed to be mounted in an instrumented panel. Mount the 

instrument in a location where its terminals will not inadvertently be touched.

•  Well ventilated locations

  Mount the instrument in well ventilated locations to prevent the instrument’s inter-

nal temperature from rising. 

  However, make sure that the terminal portions are not exposed to wind. Exposure 

to wind may cause the temperature sensor accuracy to deteriorate. To mount mul

-

tiple indicating controllers, see the external dimensions/panel cutout dimensions 

which follow. 

If mounting other instruments adjacent to the instrument, comply with 

these panel cutout dimensions to provide sufficient clearance between the instruments.

•  Locations with little mechanical vibration

  Install the instrument in a location subject to little mechanical vibration.

•  Horizontal location

  Mount the instrument horizontally and ensure that it is level, with no inclination to 

the right or left.

Front panel

of controller

Keep this angle

within 30°

Rear of

controller

30°

Note

If the instrument is moved from a location with low temperature and low humidity 

to a place with high temperature and high humidity, or if the temperature changes 

rapidly, condensation will result. Moreover, in the case of thermocouple inputs, 

measurement errors will result. To avoid such a situation, leave the instrument in the 

new environment under ambient conditions for more than 1 hour prior to using it.

Do not mount the instrument in the following locations:

•  Outdoors

•  Locations subject to direct sunlight or close to a heater

  Install the instrument in a location with stable temperatures that remain close to an 

average temperature of 23°C. Do not mount it in locations subject to direct sunlight 

or close to a heater. Doing so adversely affects the instrument.

•  Locations with substantial amounts of oily fumes, steam, moisture, dust, or 

corrosive gases

  The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely 

affects the instrument. Do not mount the instrument in locations subject to any of 

these substances.

•  Areas near electromagnetic field generating sources

  Do not place magnets or tools that generate magnetism near the instrument. If the 

instrument is used in locations close to a strong electromagnetic field generating 

source, the magnetic field may cause measurement errors.

•  Locations where the display is difficult to see

  The instrument uses an LCD for the display unit, and this can be difficult to see 

from extremely oblique angles. Mount the instrument in a location where it can be 

seen as much as possible from the front.

•  Areas close to flammable articles

  Absolutely do not place the instrument directly on flam-

mable surfaces. If such a circumstance is unavoidable 

and the instrument must be placed close to a flammable 

item, provide a shield for it made of 1.43 mm thick plated 

steel or 1.6 mm thick unplated steel with a space of at 

least 150 mm between it and the instrument on the top, 

bottom, and sides.

•  Areas subject to being splashed with water

WARNING 

Be sure to turn OFF the power supply to the controller before in-

stalling it on the panel to avoid an electric shock.

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

Operation

Guide

IM 05P01D31-11EN

UT35A/UT32A

Digital Indicating Controllers

Operation Guide

This operation guide describes installation, wiring, and other tasks required to make the 

controller ready for operation.

2nd Edition : Jun. 2010

Installation and Wiring

n

 Waste Electrical and Electronic Equipment (WEEE), 

Directive 2002/96/EC

This is an explanation of how to dispose of this product based on Waste Electrical 

and Electronic Equipment (WEEE), Directive 2002/96/EC. This directive is only valid 

in the EU.

Marking

This  product  complies  with  the  WEEE  Directive  (2002/96/EC) 

marking requirement.

This marking indicates that you must not discard this electrical/

electronic product in domestic household waste.

Product Category

With  reference  to  the  equipment  types  in  the  WEEE  directive  Annex  1,  this 

product  is  classified  as  a  “Monitoring  and  Control  instrumentation”  product.

 

Do not dispose in domestic household waste. When disposing products in the EU, 

contact your local Yokogawa Europe B.V. office.

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATION

Network Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN

YOKOGAWA CORPORATION OF AMERICA

Head office and for product sales

2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.

Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: