3-8
IM 77C01H01-10EN
3.2 Setting Pulse Output
3.2.4
LAG/LEAD/Regenerative Selection for Pulse Output of Electric Energy
[Procedure]
1. Write a value for LAG/LEAD/regenerative selection for pulse output of electric energy to
the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No.
H No.
Description
Effective Range
D0087
40087
0056
Value for LAG/LEAD/
regenerative selection for
output pulse of electric energy
0: LAG PULSE
1: LEAD PULSE
2: Regenerative PULSE
D0072
40072
0047
Setting change status
If other than 1: Invalid
If 1: Writing is executed
Default value for LAG/LEAD/regenerative selection for output pulse of electric energy:
With the optional reactive power/reactive energy measuring function: 0 (LAG PULSE)
Without the optional reactive power/reactive energy measuring function: 2 (Regenerative PULSE)
[Example]
To set a value for LAG/LEAD/regenerative selection to 1 (LEAD):
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW02D0087, 0001, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
The value for LAG/LEAD/regenerative selection for output pulse of electric energy value can be set
for the UPM100 with pulse outputs and the one with the reactive power/reactive energy measuring
function. For the UPM100 without the reactive power/reactive energy measuring function, only the
regenerative PULSE is available.