3-7
IM 77C01H01-10EN
Procedures for Setting UPM100/UPM101 Functions
3
3.2 Setting Pulse Output
3.2.3
Pulse Unit-2 of Electric Energy
[Procedure]
1. Write a pulse unit-2 of electric energy value to the D register in the table below. The data
type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No.
H No.
Description
Effective Range
D0085
40085
0054
Pulse unit-2 of electric
energy value
1 to 50,000
Unit: x 10 varh/pls
D0072
40072
0047
Setting change status
If other than 1: Invalid
If 1: Writing is executed
Default value of pulse unit-2 of electric energy: 100 (1000 varh/pls)
[Example]
To set the pulse unit-2 of electric energy value to 100 varh/pls, write “000A.”
1
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
1: The data written when the integral resolution (kWh) option is set.
[Command]
[STX] 01010WRW02D0085, 000A, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
• The pulse unit-2 of electric energy value can be set for the UPM100 with pulse outputs and the
one with the reactive power/reactive energy measuring function.
• To set the pulse unit-2 of electric energy value using the UPM100 with the integral resolution
(kWh) option via communication, set it to 1/10th the value of the displayed (true) value (e.g., set
it to 5 when setting the pulse unit-2 of electric energy value to 50 varh/pls).
The value of the UPM100 with the integral resolution (Wh) option should be the same as that of
the displayed value.