3-11
IM 77C01H01-10EN
Procedures for Setting UPM100/UPM101 Functions
3
3.3 Executing Reset Operations
3.3.2
Active Energy Reset
[Procedure]
1. To execute active energy reset, write data to the D register or the I relay in the table
below. The data type is integer.
D Register Reference No. H No. I relay
Description
Effective Range
D0060
40060
003B
I0011
Reset the active energy
(D0001 and D0002)
If other than 1: Invalid
If 1: Active energy is reset
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute active energy reset:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
[Command]
[STX] 01010WRW01D0060, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
3.3.3
Maximum/Minimum Values Reset
[Procedure]
1. To execute maximum/minimum values reset, write data to the D register or the I relay in
the table below. The data type is integer.
D Register Reference No. H No. I relay
Description
Effective Range
D0061
40061
003C
I0012
Reset the maximum/
minimum values
(D0023 to D0040)
If other than 1: Invalid
If 1: Maximum/minimum
values are reset
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute maximum/minimum values reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0061, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]