4-21
IM 77C01H01-10EN
PC Link Communication
4
4.3 Communication with Higher-level Devices
Higher-level devices are those capable of using the PC link communication protocol.
4.3.1
Communication with FA-M3 (UT Link Module)
Communication with FA-M3 is achieved by simply connecting the UPM100 to a UT link
module using the PC link communication protocol. Set the communication conditions of the
UPM100 identical to those of the UT link module.
040130E.EPS
PLC
Maximum overall cable length of 1200 m for a maximum of 31 slave stations
Model of UT link module: F3LC51-2N
Figure 4-3 Communication with UT Link Module
The UT link module function has the following two modes, which allow you to communicate
with FA-M3 without being aware of it. For more information, see the optionally available “UT
Link Module User’s Manual (IM 34M06H25-01E).”
1. Automatic mode
This mode enables the instruments’ fixed devices (those that cannot be specified by the
user) to be constantly refreshed by reading from and/or writing to them. The fixed devices
are D0001 to D0022, and the read areas cannot be written to.
2. Manual mode (constant access)
This mode reads and refreshes the instrument’s devices (those that can be specified by the
user).
See Also
The devices mentioned here are D registers and I relays. For more information on D
registers and I relays, see Chapters 6 and 7.