<3. INSTALLATION>
3-2
All Rights Reserved. Copyright © 2003, Rota Yokogawa
IM 01R01B30-00E-E 8th edition November 01, 2019-00
Fig. 3-1 RAKD with Quickon connector, electronic transmitter and standard limit switch
Fig. 3-2 RAKD with Quickon connector, electronic transmitter and fail-safe limit switch
1
2
1
2
1
2
L-
L+
F
G
T
-
+
BU
BN
S
-
P
+
P S
Rotameter RAKD
Pulse output or one limit switch
alternatively
Power supply acc. EN 60947-5-6 (Namur)
T, S: QUICKON connector
4 to 20 mA
Power supply
U = 14 to 30 V DC
+ -
R
L
≤ U - 14 V
20 mA
Output 4 to 20 mA
*)
EN 60947-5-6 (Namur)
Pulse output
*)
Limit switch /K1, /K2
*)
+
-
+
-
Alternatively transmitter power supply option /UT
can be used.
Alternatively power supply option /WxA can be used.
1
2
EN 60947-5-6 (Namur)
L-
L+
F
G
T
Rotameter RAKD
Electronic transmitter, -E
4 to 20 mA
Power supply
U = 14 to 30 V DC
+ -
R
L
≤ U - 14 V
20 mA
Output 4 to 20 mA
T, S: QUICKON connector
Fail safe power supply
+
-
Alternatively power supply option /WxE can be used.
Limit switch /K6, /K7
1
2
-
+
BU
BN
S
+
-
Alternatively transmitter power supply option /UT
can be used.
Fig. 3-3 RAKD with Quickon connector and standard limit switches
Rotameter RAKD -T80
-
+
+
-
BU
2
BN
BU
BN
1
2
1
MIN
F
MAX
S
T
EN 60947-5-6 (Namur)
Limit switches, /K1, /K2, /K3
Power supply acc. EN 60947-5-6 (Namur)
+
-
Power supply acc. EN 60947-5-6 (Namur)
+
-
T, S: QUICKON connector
Alternatively power supply option /WxA or /WxB can be used.
Rotameter RAKD -T80
-
+
+
-
BU
2
BN
BU
BN
1
2
1
MIN
F
MAX
S
T
EN 60947-5-6 (Namur)
Limit switches, /K6, /K7, /K8
Fail safe power supply
+
-
Fail safe power supply
+
-
T, S: QUICKON connector
Alternatively power supply option /WxE or /WxF can be used.
Fig. 3-4 RAKD with Quickon connector and fail-safe limit switches