Transmitter
General Instruction Manual
Wiring
IM 01U10B00-00EN-R, 3rd edition, 2018-07-09
57 / 90
Active pulse
output
P/Sout
Connection of an electronic counter
Maximum voltage and correct polarity must be observed for wiring.
Value
Load resistance
> 1 kΩ
Internal power supply
24 V
DC
±20 %
Maximum pulse rate
10000 pulses/s
Frequency range
0 – 12.5 kHz
P/Sout+
P/Sout-
24 V
0 V
ROTAMASS
2
1
Fig. 41:
Active pulse output connection
P/Sout
①
Load resistance
②
Electronic counter
Connection of an electromechanical counter
Value
Maximum current
150 mA
Average current
≤ 30 mA
Internal power supply
24 V
DC
±20 %
Maximum pulse rate
2 pulses/s
Pulse width
20, 33, 50, 100 ms
P/Sout+
P/Sout-
24 V
0 V
1
ROTAMASS
2
Fig. 42:
Active pulse output
P/Sout
connection with electromechanical counter
①
Protective diode
②
Electromechanical counter