5-11
IM 01F06A00-01E
5. PARAMETER SETUP
(3) Item C : BASIC SETUP
These items are for the basic parameters with setting before
shipment.
The parameters which are set in B are not necessary to set in
C.
A value in “( )” is the data corresponding to indicator.
The parameters, C20 to C50, are not indicated
when option code “/MV” is selected and
parameter item is selected in F10 except
“Monitor only” or “Not Use”.
[C10: TAG NO] Tag. No
Set Tag. No. (16 characters)
Available characters are as follows.
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a
b c d e f g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 6 7
8 9 . SPACE / - , +
*
) (
’
& % $ # “ !
[C20:FLUID] Flowrate unit
Set the flowrate unit below.
T050403.EPS
LIQUID : Volume
(0)
GAS/STEAM : Volume (1)
LIQUID : Mass
(2)
GAS/STEAM : Mass (3)
GAS : STD/Normal (4)
Volumetric flow of Iiquid measuring
Volumetric flow of gas or steam measuring
Mass flow of liquid measuring
Mass flow of gas or steam measuring
Volumetric flow at Standard condition
Item
Description
The following items should be done in case of
which “C20” is “LIQUID : Volume” or “GAS/
STEAM : Volume”.
[C22:VOLUME UNIT] Volumetric unit
Select the unit of volumetric flow from m
3
(0), km
3
(1), l(2),
cf(3), mcf(4), def(5), USgal(6), kUKgal(9), bbl(10),
mbbl(11), kbbl(12).
The following items should be done in case of
which “C20” is “LIQUID: Mass” or “GAS/
STEAM : Mass”
[C25:DENSITY UNIT] Density Unit of Flow
measurement
Select the unit of density from kg/m
3
(0), lb(1), lb/USgal(2),
lb/UKgal(3).
[C26:DENSITY f] Density at normal operation
conditions
Set the density value of the fluid at operating condition for
mass flow unit.
[C27:MASS UNIT] Mass flowrate unit
Select the mass flowrate unit from kg(0), t(1), lb(2), k lb(3).
The following item should be done in case of
which “C20” is “GAS/STEAM : Volume”.
[C30:TEMP UNIT] Fluid temperature unit at
operating conditions
Select temperature unit at operating condition from
“degC (0), degF (1)”.
[C31:TEMP f] Fluid temperature at operating
conditions
Set fluid temperature at operating condition.
Range is -196 to 450
°
C
The following items should be done in case of
which “C20” is “GAS/STD : Normal”.
[C32:TEMP b] Fluid temperature at standard/
normal conditions
Set the values of Fluid temperature at standard condition.
[C33:PRESS UNIT] Pressure unit
Select the unit of pressure from “MPa abs(0), kPa abs(1), kg/
cm2 abs(2), bar abs(3)”.
[C34:PRESS f] Absolute pressure at operating
conditions
Set the absolute pressure at operating condition.
[C35:PRESS b] Absolute pressure at standard/
normal condition
Set the absolute pressure at normal condition.
[C36:DEVIATION] Deviation factor
Set deviation factor.
[C37:STD/NOR UNIT] Volumetric unit at normal
conditions
Select volumetric unit at normal condition from Nm
3
(0),
kNm
3
(1), MNm
3
(2), Nl(3), Sm
3
(4), Km
3
(5), Mm
3
(6), Sl(7),
scf(8), kscf(9), Mscf(10).
N: Normal
S: Standard
[C40:TIME UNIT] TIME UNIT
Select time unit from “/s(0), /m(1), /h(2), d(3)”
[C45:FLOW SPAN] Flowrate span
Set the required span with a numerical value.
[C50:DAMPING] Damping time constant
Set damping time constant values from 0 to 99s.