4-12
IM 01F06A00-01E
4. BASIC OPERATING PROCEDURES
(2) Change the Pulse Output to Alarm Output.
F040505.EPS
Enter menu item, and press
“ ” key.
Move the inverse video bar
to “B : EASY SETUP”.
Item B menu is displayed.
Move the inverse video bar
to “B20 : CONTACT OUT”.
Pressing “ENTER”, cause
the data setup screen to be
displayed.
If the security screen
appears,
enter the security code.
Move the inverse video bar
to “ALARM”.
2 Times
4 Times
Pressing the enter key,
inverse video bar is flashed.
The data setting can be
completed.
If data setting is missing,
press “
F3
” key and rewrite
the data.
Setting is completed.
The screen returns to the
preceding screen when the
“
F4
” (ESC) key is pressed.
MENU
A:DISPLAY
B:EASY SETUP
C:BASIC SETUP
D:AUX. SETUP
E:METER SETUP
H:ADJUST
HOME SET ADJ ESC
PARAM
B10:FLOW SPAN
100 m3/h
B15:DAMPING
4 sec
B20:CONTACT OUT
SCALED PULSE
DATA DIAG PRNT ESC
PARAM
B10:FLOW SPAN
100 m3/h
B15:DAMPING
4 sec
B20:CONTACT OUT
SCALED PULSE
DATA DIAG PRNT ESC
PARAM
B10:FLOW SPAN
100 m3/h
B15:DAMPING
4 sec
B20:CONTACT OUT
ALARM
DATA DIAG PRNT ESC
SET
B20:CONTACT OUT
SCALED PULSE
< OFF >
< SCALED PULSE >
<UNSCALED PULSE>
ESC
SET
B20:CONTACT OUT
SCALED PULSE
<UNSCALED PULSE>
< FREQUENCY >
< ALARM >
ESC
SET
B20:CONTACT OUT
SCALED PULSE
ALARM
Print off
F2:printer on
FEED POFF NO
SET
B20:CONTACT OUT
ALARM
FEED NO OK
IMPORTANT
After setting a parameter, keep the power on for at
least 30 seconds.
If the power of flowmeter is turned off, a parameter
setting is released.