18
IM 04L41B01-02E
Operation Example in the Setting Mode: Changing the Input Range
Set the input range of channel 2 to thermocouple type T and 0.0 to 400.0
°
C.
Type T
thermocouple
Channel 2
DX
1
.
Display the operation mode screen.
2
.
Press
MENU
once to display the setting menu.
3
.
Press the
down arrow key
once to select
Meas channel
.
4
.
Press the
right arrow key
once.
Select the Range, Alarm
5
.
Press
DISP/ENTER
once.
Select First-CH
6
.
Press the
2
soft key once. The
Last-CH
is also set to
2
.
7
.
Press the
down arrow key
once to move the cursor to
Mode
.
Basic Operation