74
IM 04L41B01-02E
Communication (Serial)
Setup Item
Selectable Range or Selections
Default Value
Setting
Basic settings
Baud rate
1200/2400/4800/9600/19200/38400
9600
Data length
7/8
8
Parity
Odd/Even/None
Even
Handshaking
Off:Off/XON:XON/XON:RS/CS:RS
Off:Off
Address
1 to 99
1
Protocol
Normal/Modbus/Modbus-M
Normal
Modbus master > Basic settings
Read cycle
125ms/250ms/500ms/1s/2s/5s/10s
1s
Timeout
125ms/250ms/500ms/1s/2s/5s/10s/1min
1s
Retrials
Off/1/2/3/4/5/10/20
1
Inter-block delay
Off/5ms/10ms/15ms/45ms/100ms
Off
Auto recovery
Off/1min/2min/5min/10min/20min/30min/1h
2min
Modbus master > Command settings
Master command number
1-8/9-16
1-8
1 to 16
Off/R/R-M/W/W-M
Off
First
Depends on the command type.
–
Last
Depends on the command type.
–
Addr.
1 to 247
1
Regi.
Numerical value
30001
Type
INT16/UINT16/INT32_B/INT32_L/UINT32_B/ INT16
UINT32_L/FLOAT_B/FLOAT_L
Status relay
Setup Item
Selectable Range or Selections
Default Value
Setting
Memory/Media status
On/Off
Off
Measurement error
On/Off
Off
Communication error
On/Off
Off
Memory stop
On/Off
Off
End
Setup Item
Selectable Range or Selections
Default Value
Setting
Do you want to store and
Yes/No/Cancel
–
make the new settings take effect?
Setup Items and dDefault Values