6. OPERATION VIA BRAIN TERMINAL
Select “PROVIDED” in “D02:FL USER SEL.”
Default:NOT PROVIDED
In “D03:FL USER SPAN” set the value of 100% flow rate to be
displayed in “A20:FLOW RATE” The user-defined unit is set in
“D10:FL USER UNIT” Default:100.0
Set the user-defined unit in “D10:FL USER UNIT”
The instantaneous flow rate in user-defined unit can be displayed in
“A20:FLOW RATE”
DIAG
DATA
Display
Description
PARAM
D02:FL USER SEL
PROVIDED
D03:FL USER SPAN
20000.0
D10:FL USER UNIT
kg/h
DATA
DIAG
ESC
PARAM
A10:FLOW RATE(%)
1 0 0 . 0 %
A20:FLOW RATE
2 0 0 0 0 . 0 k g / h
A30:TOTAL
0
ESC
PRNT
(2) User-Defined Unit for Totalization Value
User-defined unit can be added to the totalization display in “A30 TOTAL”
Set the user-defined unit in “E10:TL USER UNIT”
The totalization value in user-defined unit can be displayed in
“A30:TOTAL”
DIAG
DATA
Display
Description
PARAM
E04:TOTAL SET
INHIBIT
E05:TL SET VALUE
0
E10:TL USER UNIT
kg
DATA
DIAG
ESC
PARAM
A10:FLOW RATE(%)
1 0 0 . 0 %
A20:FLOW RATE
2 0 0 0 0 . 0 k g / h
A30:TOTAL
4 0 0 0 0 k g
ESC
6.7 Other Important Points
(1) The automatic power-off function turns the BT200 off automatically with no key
access for about 5 minutes or more. However, this function does not operate when
the BT200 is displaying “A10:FLOW RATE (%)” or “A20:FLOW RATE”
(2) When “A10:FLOW RATE (%)” or “A20:FLOW RATE” is displayed, the data are
updated every 5 seconds.
(3) UPLOAD/DOWNLOAD functions which can copy the setting date between
ADMAG SE and BT200 are provided. (For details, see the “BT200 Instruction
Manual IM 1C0A11-01E.”)
Parameters that can be copied are as follows:
B02 DAMPING, B03 FLOW SPAN, B04 FLOW UNIT, B05 TIME UNIT,
B06 SIZE UNIT, B07 NOMINAL SIZE, B10 OUTPUT FUNC, B11 4-20 ALM OUT,
D01 DISP SELECT, D02 FL USER SEL, D03 FL USER SPAN,
D10 FL USER UNIT, E01 TOTAL UNIT, E02 TOTAL SCALE,
E03 TOTAL LOWCUT, E04 TOTAL SET, E05 TL SET VALUE,
E10 TL USER UNIT, F01 PULSE UNIT, F02 PULSE SCALE,
F03 PULSE LOWCUT, F04 PULSE WIDTH, G01 4-20 LOW CUT,
G02 4-20 LOW LMT, G03 4-20 H LMT