![YMGI WMMS-09ES-V2B2 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/ymgi/wmms-09es-v2b2/wmms-09es-v2b2_installers-instruction-and-users-manual_3603957016.webp)
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
YMGI: Your Modern Green Idea
16
MINI WALL MOUNT SYSTEMS - SPECIFICATION BRIEFS
Unit Specifications and Engineering
Submittal G2 Models
AC Power Supply 208~240V/1Ph/50 or 60HZ for Non-Stop Guaranteed Cooling/Heating
Min.-Max. Solar
Panel Qty.
W/V
2-8x250W/40V
2-8x250W/40V
2-8x250W/40V
2-8x300W/40V
2-8x300W/40V
2-8x300W/40V
Voltage Between PV+ and PV-
50-350VDC
50-350VDC
50-350VDC
50-350VDC
50-350VDC
50-350VDC
Model No.-System
WMMS-09KS-V2B(56)2 WMMS-12KS-V2B(56)2 WMMS-18KS-V2B(56)2 WMMS-24KS-V2B(56)2 WMMS-30KS-V2B(56)2 WMMS-36KS-V2B(56)2
Model No.- Indoor Unit
WMMS-09ES-V2B(56)2 WMMS-12ES-V2B(56)2 WMMS-18ES-V2B(56)2 WMMS-24ES-V2B(56)2 WMMS-30ES-V2B(56)2 WMMS-36ES-V2B(56)2
Model No.- Outdoor Unit
WMMS-09CS-V2B(56)2 WMMS-12CS-V2B(56)2 WMMS-18CS-V2B(56)2 WMMS-24CS-V2B(56)2 WMMS-30CS-V2B(56)2 WMMS-36CS-V2B(56)2
Nominal Ton-Cooling
Ton
0.75
1
1.5
2
2.5
3
Performance
Capacity
Rating
Cooling
Btu/h
9000
12000
18000
24000
30000
36000
W
2600
3500
5200
7200
9000
10000
Heating
Btu/h
10000
13000
20000
27000
34000
40000
W
2800
3700
5400
7900
10000
11000
Noise
Indoor
dB(A)
40
42
44
46
47
48
Outdoor
dB(A)
50
52
55
58
59
60
Air Circulation
cfm
264.86
323.72
441.43
618
363.74
735.72
EER
W/W
10.2
9.7
9.5
9.4
9.3
9.3
SEER
Btu/h/w
Up to 35
Up to 34
Up to 34
Up to 33
Up to 33
Up to 32
COP
W/W
5.8
5.2
4.9
4.8
4.7
4.7
HSPF
Btu/h/w
Up to 23
Up to 23
Up to 24
Up to 25
Up to 25
Up to 25
Operating Range
Indoor Unit
61-88°F
61-88°F
61-88°F
61-88°F
61-88°F
61-88°F
Outdoor Ambient
Cooling
23-132°F
23-132°F
23-132°F
23-132°F
23-132°F
23-132°F
Heating
5-75°F
5-75°F
5-75°F
5-75°F
5-75°F
5-75°F
Design pressure
PSI
550 / 340
550 / 340
550 / 340
550 / 340
550 / 340
550 / 340
Refrigerant Oil
VG74
VG74
VG74
VG74
VG74
VG74
Refrigerant
R410A
R410A
R410A
R410A
R410A
R410A
Compressor
ROTARY
ROTARY
ROTARY
ROTARY
ROTARY
ROTARY
Liquid side
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
Gas side
3/8"
1/2"
1/2"
5/8"
5/8"
5/8"
DC Connection / Wire
MC4/AWG 8/10
MC4/AWG 8/10
MC4/AWG 8/10
MC4/AWG 8/10
MC4/AWG 8/10
MC4/AWG 8/10
Power Consumption
Rated Power Input
W
450
750
950
1250
1550
1800
Rated Current
A
2.05
3.41
4.32
5.68
6.86
7.96
IDU Power Supply
208-230VAC
208-230VAC
208-230VAC
208-230VAC
208-230VAC
208-230VAC
IDU Current / Watts
0.05A/15.5W
0.06A/18.6W
0.09A/27.9W
0.12A/37.2W
0.17A/53.2W
0.21A/65.1W
Dimensions
Indoor Unit
(WxHxD)
NET
in.
30.31” x 9.84”
x 7.87”
30.31” x 9.84”
x 7.87”
35.43” x 11.81” x
8.27”
35.43” x 11.81” x
8.27”
46.06” x 12.99” x
10.24”
46.06” x 12.99” x
10.24”
Shipping
In.
33.46” x 12.60” x
11.02”
33.46” x 12.60” x
11.02”
38.98” x 14.96” x
11.02”
38.98” x 14.96” x
11.02”
50.00” x 16.54” x
13.39”
50.00” x 16.54” x
13.39”
Outdoor
Unit
(WxHxD)
NET
in.
29.92” x 21.26” x
10.24”
29.92” x 21.26” x
10.24”
33.46” x 22.83” x
11.81”
33.86” x 28.74” x
12.60”
33.86” x 28.74” x
12.60”
33.86” x 28.74” x
12.60”
Shipping
in.
35.04” x 23.23” x
14.17”
35.04” x 23.23” x
14.17”
39.17” x 25.59” x
15.35”
40.35” x 31.10” x
15.55”
40.35” x 31.10” x
15.55”
40.35” x 31.10” x
15.55”
Weight
Indoor Unit Net/Gross
lbs.
24.25 / 28.66
28.66 / 33
37.5 / 41.88
41.88 / 48.5
48.5 / 50.7
48.5 / 50.7
Outdoor
Unit
Net/Gross
lbs.
83.8 / 88.2
99.2 / 105.8
105.8 / 121.25
123.5 / 136.7
125.7 / 143.3
127.9 / 143.3
Notes:
1.
Performance rated for matched system at standard conditions-cooling ID 80/67°F, OD 95°F; heating ID 70/60°F, OD 47/43°F, 25 ft. copper
lines and IDU 7ft. above ODU.
Unit performance varies when weather changes from the standard one.
2.
Select equipment capacity sizes per space load calculation schedule and cooling & heating hours. Not to over size or under size equipment.
3.
Watch unit operation during extreme weather conditions in summer and winter. Wind baffle helps system cooling & heating performance in low
ambient temperature ranges.
4.
Heating capacities up to 85% @ 17°F ambient temperature, up to 60% @ -4°F varying upon geographic location and actual installation.