DIAGONSIS CODE, POSSIBLE CLAUSES, AND SUGGESTED ACTIONS TO 
USER AND TECHNICIAN

DIAGNOSIS CODE & TROUBLE-SHOOTING GUIDELINE

Codes

Descriptions

Possible Reasons

Suggestion to User

Technician Trouble-Shooting

E1

Condensate Full in drain pan

Dain pan dirty, drain hose 
clogging, water level switch 
failure, loose connection, 
bad control board/
components, etc.

Check if drain hose is 
clogged; if not, need to call 
your installing or service 
technician.

E2

Indoor air temp. sensor failure

Bad temperature sensor; 
loose connection, damaged 
wires, bad control board/
components, etc.

E3

Indoor coil copper tube 
sensor failure

Bad temperature sensor; 
loose connection, damaged 
wires, bad control board/
components, etc.

Lift up grille/cover, to check 
if the sensor looks bad or 
drops out of holding socket/
pocket; or, to call installing 
or service technician.

E4

Abnormal cooling

E5

Abnormal heating

Dirty filters/coils, refrigerant 
leaks over time, pipe too 
long, kinks or clogging in 
pipe line or valves, pipe 
damage, sensor failure, 
compressor or board or 
other component failures, 
etc.

1) Regularly check and
    clean indoor unit filters, 
    indoor and outdoor coils.

2) The service valves at
    outdoor unit should be 
    generally cool at cooling 
    mode, hot at heating 
    mode;

3) Call your installing or
    service technician to 
    check unit.

E6

Cooling-outdoor coil low 
temp. protection

Outdoor too cold to run 
cooling mode, windy, too 
much refrigerant, short 
piping, etc.

E7

Cooling-Indoor coil anti-
freeze protection

Dirty filter/coils, indoor fan 
motor failure, loose blower 
wheel/motor connection, too 
much or less refrigerant, 
pipe/cap. tube/valve 
clogging, etc.

E8

Heating-outdoor coil high 
temp. protection

Outdoor temperature too 
warm to run heating mode, 
too much refrigerant, short 
piping, etc.

E9

Heating-indoor coil anti-to 
hot protection

Dirty filter/coils, indoor fan 
motor failure, loose blower 
wheel/motor connection, too 
much refrigerant, pipe/cap. 
tube/valve clogging, etc.

E0

Heating-outdoor coil too 
cold protection

Outdoor temperature is too 
cold to run heat pump/
heating.

1) Shut off the unit;

2) Cooling, wait until 
    weather allows the unit 
    to re-start, or switch to 
    alternative cooling 
    equipment which allows 
    lower ambient cooling;

3) Heating, wait until 
    weather allows the unit 
    to re-start, or switch to 
    base-board heater, gas 
    furnace or other 
    alternative heating 
    sources during cold 
    hours/days.

1) Check if these are
    caused by installation or 
    component failure;

2) There could be nothing 
    abnormal, but the unit is 
    at protection mode, which 
    means the current 
    ambient temperature is 
    not proper to run the unit;

3) If there is something
    wrong, need to find all 
    the clauses and correct 
    or fix the problems and 
    not to leave any bugs.

1) Shut off power;

2) Follow possible clauses 
    listed at the left, to check 
    one by one;

3) To save time for quick 
    diagnosis as much as 
    posible, suggest your 
    technician to make 
    appointment with YMGI 
    tech. support, and call us  
    while the techician is at 
    job site. 

4)  Better to check the unit, 
    get problems and model 
    model #, and serial # 
    ready, before calling 
    YMGI tech. support.

5) Need the technician 
    physically, at the job site, 
    use right tools and 
    experience, to find all the 
    clauses and correct or fix 
    the problems and not to 
    leave any bugs.

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

P39 OF 44

P40 OF 44

CHECK AFTER INSTALLATION AND TEST OPERATION

1) Before test operation

(1) Do not turn on power before installation is finished completely.
(2) Electric wires must be connected correctly and securely.
(3) Cut-off valves of the connection pipes should be back seated/tunned on.
(4) All the impurities such as scraps and thrums must be cleared out of the unit.

2) Test operation method

(1) Switch on power, press "ON/OFF" button on the wireless remote control to start the operation
(2) Press MODE button, to select the COOL, HEAT (not available for cooling only unit is ), FAN and so on to check :
     * All the functions (to make sure the unit functions correctly and poroenty).
     * Refrigerant (pressures/temperatures at sericea values/pipes should be good).
     * Drainage (condensate/water flow should be dripping out of drainage pipe ONLY).
     * Noise (there should be no abnormal symbol)

Has the been unit positioned firmly? 

The unit may drop, shake or emit noise.

Have you done the refrigerant leakage test?

It may cause insufficient cooling(heating)
capacity.

Is heat insulation sufficient?

It may cause unexpected condensate and 
dripping.

Is drainage pipe tested ?

 It may cause leakage or unexpect dripping.

Is the voltage in accordance with the rated
voltage marked on the nameplate?

It may cause electric malfunction
or damage to the part/unit.

Is the electric wiring and piping
connection installed correctly and securely?

It may cause electric malfunction
or damage to the part/unit.

Has the unit been connected to a secure
earth connection?

It may cause electrical leakage.

Is the power cord specified properly per 
NEC codes ? 

It may cause electric malfunction
or damage to the part/unit.

Is the air inlet and outlet been cleared?

It may cause insufficient cooling(heating)
capacity, and unexpected noise.

Has charge be adjusted to mateh the 
and refrigerant capacity been recorded?

The refrigerant unit noise, iced up 
overheat insufficient cooling or heating

Items to be checked 

Possible malfunction

CHECK AFTER INSTALLATION

TEST OPERATION

1) Put back all covers, screws removed during installation 
    and start-up. 
2) Properly note, mark, organize and secure wires.

3) Caulk the opening to weatherproof level at opening frame 
    both inside and outside.
4) Do a final visual inspection.

5) Teach or instruct owner or users how to correctly operate 
    the system and answer their questions. 

6) Check against all items in Product/Warranty Registration 
    Card and sign it for the owner.

FINISH INSTALLATION

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание M2 SERIES

Страница 1: ...his product is designed and manufactured free from defects in material and workmanship under the normal use and maintenance Installation operation maintenance and service shall follow professional pra...

Страница 2: ...y parts may be new or refurbished All parts are tested and approved before shipping At no time does the YMGI Group warrant labor cost of any type Warranty will start from the date of successful instal...

Страница 3: ...nit for condensate leakage and refrigerant leakage before and after connecting them 28 Do you list the working details in the invoice and leave a copy to the customer 19 Did you charge the inter conne...

Страница 4: ...roperly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLL...

Страница 5: ...e ability to claim freight damage is lost and YMGI will not replace the unit on this basis Contact the distributor or YMGI report the damage by forwarding the marked delivery receipt copy and pictures...

Страница 6: ...Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent bac...

Страница 7: ...ed to keep from cold air blowing into propeller fan blade against airflow and so help unit work better in both AC cooling and HP heating mode in colder weather ranges IMPORTANT NOTES FOR UNIT OPERATIO...

Страница 8: ...n the ground Once stacking or bracket kit is used some outdoor units can be stacked 2 or 3 units high upon unit size and applications Air is discharged horizontally quietly and smoothly These units ar...

Страница 9: ...X24K 32B WMMS 2X30K 32B WMMS 09E F 32B WMMS 09 12E F 32B WMMS 12E F 32B WMMS 18E F 32B WMMS 24E F 32B WMMS 30E F 32B WMMS 2X09C 32B WMMS 0912C 32B WMMS 2X12C 32B WMMS 2X18C 32B WMMS 2X24C 32B WMMS 2X3...

Страница 10: ...4K 2 30K 3 09K 2 12 18K 3 12K 2 18 24K 2 09 12K 2 09 12 K 2 12 24K 3 12 24K Varies Varies Varies UNIT ENGINEERING SUBMITTALS MECHANIAL 09K 12K W H D 30 9 36 2 10 6 10 6 7 8 7 9 18K 24 36K 40 2 12 4 9...

Страница 11: ...thly without any abnormal noise or restriction 4 Fan wheel roration at outdoor unit should rotate freely and smoothly without any abnormal noise or restriction 5 No kinking or other leaking potentials...

Страница 12: ...ctricians only following NEC codes and manufacturer instructions CONNECTION OF WIRES SINGLE ZONE WIRING AT INDOOR UNIT AND OUTDOOR UNITS Open the front cover panel Remove screws from electrical box co...

Страница 13: ...taken into consideration when the connections of power cable are made such as the ambient temperature direct exposure to heat dirext exposure to sunlight The specifications for the power cable refer...

Страница 14: ...CLEARANCE REQUIRED AROUND UNITS SINGLE ZONE CLEARANCE REQUIRED AROUND UNITS DUAL ZONE Indoor unit B Indoor unit A SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainabl...

Страница 15: ...ndoor unit C SYSTEM LAYOUT INSTALLATION CLEARANCE Indoor unit A Indoor unit B Indoor unit C Indoor unit D SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainable and Ef...

Страница 16: ...screws Align mounting plate holes with those holes drilled on the wall and put anchors or screws into the holes to secure mounting plate STEPS TO MOUNT PLATE a b c Drill mounting holes to make sure a...

Страница 17: ...rear side of plastic casing Snap the plastic casing bottom into the mounting plate gently Sealed with putty Secure the piping wiring set with clamp Trim the extra portion 2 in or less from floor 18 18...

Страница 18: ...35 45 CONNECT REFRIGERANT PIPES BETWEEN INDOOR AND OUTDOOR UNITS Firstly connect copper tubes at indoor unit Bend pipes by tools but not by hands Extra length is needed for future service REFRIGERANT...

Страница 19: ...ipes Over length soft pipes will lead to irregular bending Undersize bending will damage the soft pipe Short soft pipes will have them bending undersize it s not allowed INLTS STRT COUP COUP H OFST EL...

Страница 20: ...ks 1 Blink lit for 0 5 sec then off for 0 5 sec then lit for 0 5 sec 2 E4 Code Outdoor ambient temperature is too low do not to run unit during severe cold weather Refrigerant at low level users need...

Страница 21: ...hnician to make appointment with YMGI tech support and call us while the techician is at job site 4 Better to check the unit get problems and model model and serial ready before calling YMGI tech supp...

Страница 22: ...STALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS IMPORTANT NOTES FOR INSTALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS YMGI Engineered Comfort Products for A Sustainable and Efficient...

Страница 23: ...original licensed installer or current service contractor should be contacted first of all since they installed the unit and or know more details than anybody else They will check the unit and find o...

Отзывы: