HEIGHT LIMITS OF INDOOR AND OUTDOOR UNITS

* Either the indoor unit or the outdoor unit can be higher, but the height difference must comply the stated r
  equirements.

* Try to reduce the bending of the piping line as much as possible so as to avoid possible negative impacts upon 
   the performances of the units.

Indoor unit

Outdoor unit

Lift

* Make P-trap if elevation drop difference is more than 25", as illustrated below.  

Indoor unit

Outdoor unit

Drop

P-Trap

18 Ft.

Refrigerant Pipe Min/Max. Length, Rise and Drop Height 

1,000 Btu/h

09-12

18-24

30-36

Max. Length (Ft.)

50

75

100

Max. Rise Height (Ft.)

20

25

35

Max. Drop Height (Ft.)

28

35

50

Min. Length (Ft.)

15

15

15

Locate the central hole at the stud (firn structure)

At least 12"

18" or more 
from sidewall

Respect the slope

Plumb

Mounting Plate

Anchors of self-
tappping screw

18" or 

more from 

sidewall

Install Mounting Plate and Drill Hole for Combination of Copper Line/Wire Cable/Drain Hose

NOTES: 

Anchors must be put into the holes, where the solid 
arrows are pointing, as shown above, to secure the 
mounting plate firmly and to hold the weight of indoor 
unit. If more screws/anchors are to be used, make 
sure to keep the two holes close to each other, at 
least 2 inches apart.

Mounting plate should be attached to the structural 
part of the wall. Minimum clearance, as shown below, 
is required in order to ensure proper airflow and 
enough service room.

INSTALLATION-INDOOR UNIT

      INSTALL WALL MOUNT PLATE

* Check unit to make sure the unit is good shape and ready to install.

* Check to make sure the installation location is firm enough to hold the weight of the whole unit and is 
  convenient to installation, maintenance, service and close to the indoor unit but not causing noise or airflow 
  issues to neighbour.

* Install Indoor unit. Enough anchor bolts/nuts shall be used to secure mounting plates for indoor units. 
  Brackets should be at level position.

Mark drill positions. At least 4 anchor holes, one at each perimeter corner of the plate are needed to secure the 
plate, where the bold arrows are pointing, as shown in the picture above. Refer to the specification sheet for 
unit weight so that enough anchors are installed at proper positions.

Pre-drill guiding holes where are marked for anchors or screws on the wall

Confirm the position of the holes and finish drill to the depth needed for anchors (NOT for screws)

Align mounting plate holes with those holes drilled on the wall and put anchors or screws into the holes to 
secure mounting plate.

STEPS TO MOUNT PLATE:

a

b

c

Drill mounting holes 
to make sure at least 
either one of three 
dimensions a, b and 
c is 16" center to 
center.

If pipes need to come out of the right side (facing 
the front of indoor unit) of the indoor unit, snap off 
portion

1

on plastic casing.

If pipes need to come out of the bottom side 
(facing the front of indoor unit) of the indoor unit, 
snap off portion

2

on plastic casing.

If pipes need to come out of the left side (facing 
the front of indoor unit) of the indoor unit, snap off 
portion

3

on plastic casing.

Hole Diameter: 2.5~3 In

Align ruler with straight line

Insert ruler

DRILL 3IN HOLE FOR PIPING/WIRING/DRAIN

Locate the centre where the hole will need to 
drilled.

Drill the holes of 2.5-3Inch diameter. A down pitch 
about 1/4" per foot, as illustrated below, is needed 
for the hole, in order to drain the condensate 
properly.

PREPARE INDOOR UNIT- COPPER LINE SET/DRAIN HOSE

1

2

3

INSTALL DRAIN PIPE AT INDOOR

The drain hose must be placed beneath the copper 
pipes and MUST NOT be hunched or bended 
sharply.                                                 

Do not pull the drain hose too hard, otherwise it 
may get broken.

Before passing drain hose through the hold, wrap 
with insulation to keep from possible damage.

The copper pipe and the drain hose must be 
wrapped by piping wrap. 

Insulation pad (underlay) should be used where 
the pipe contacts the wall.

Slice the insulation before 
bending.     

Hold the 90 degree bend root, 
bend one tube one time, slowly, 
no quicker than 10 seconds/90 
degree bend.

If pipes need to come out of the rear side (facing 
the front of indoor unit) of the indoor unit, no need 
to snap off anything.

If pipes need to be rerouted to a different direction 
from the one preset at factory (towards left side, if 
facing the front cover of indoor unit), lay down the 
indoor unit on soft cushion or foam. Don't rub the 
plastic casing.

In order to keep from pipe damage, need to bend 
the copper tubing set gently and slowly (finish 
bending no less than 10 seconds/90 degree), by 
holding at the root of the original 90 degree bend 
nicely and firmly. Don't rub two copper lines during 
bending. Better to cut off the insulation and bend 
the two pipes one by one, not two together.

Drain hose coming with indoor unit

Drain hose extending to drain line

PREPARE INDOOR UNIT- COPPER LINE SET/DRAIN HOSE

INSTALLATION-INDOOR UNIT

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание M2 SERIES

Страница 1: ...his product is designed and manufactured free from defects in material and workmanship under the normal use and maintenance Installation operation maintenance and service shall follow professional pra...

Страница 2: ...y parts may be new or refurbished All parts are tested and approved before shipping At no time does the YMGI Group warrant labor cost of any type Warranty will start from the date of successful instal...

Страница 3: ...nit for condensate leakage and refrigerant leakage before and after connecting them 28 Do you list the working details in the invoice and leave a copy to the customer 19 Did you charge the inter conne...

Страница 4: ...roperly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLL...

Страница 5: ...e ability to claim freight damage is lost and YMGI will not replace the unit on this basis Contact the distributor or YMGI report the damage by forwarding the marked delivery receipt copy and pictures...

Страница 6: ...Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent bac...

Страница 7: ...ed to keep from cold air blowing into propeller fan blade against airflow and so help unit work better in both AC cooling and HP heating mode in colder weather ranges IMPORTANT NOTES FOR UNIT OPERATIO...

Страница 8: ...n the ground Once stacking or bracket kit is used some outdoor units can be stacked 2 or 3 units high upon unit size and applications Air is discharged horizontally quietly and smoothly These units ar...

Страница 9: ...X24K 32B WMMS 2X30K 32B WMMS 09E F 32B WMMS 09 12E F 32B WMMS 12E F 32B WMMS 18E F 32B WMMS 24E F 32B WMMS 30E F 32B WMMS 2X09C 32B WMMS 0912C 32B WMMS 2X12C 32B WMMS 2X18C 32B WMMS 2X24C 32B WMMS 2X3...

Страница 10: ...4K 2 30K 3 09K 2 12 18K 3 12K 2 18 24K 2 09 12K 2 09 12 K 2 12 24K 3 12 24K Varies Varies Varies UNIT ENGINEERING SUBMITTALS MECHANIAL 09K 12K W H D 30 9 36 2 10 6 10 6 7 8 7 9 18K 24 36K 40 2 12 4 9...

Страница 11: ...thly without any abnormal noise or restriction 4 Fan wheel roration at outdoor unit should rotate freely and smoothly without any abnormal noise or restriction 5 No kinking or other leaking potentials...

Страница 12: ...ctricians only following NEC codes and manufacturer instructions CONNECTION OF WIRES SINGLE ZONE WIRING AT INDOOR UNIT AND OUTDOOR UNITS Open the front cover panel Remove screws from electrical box co...

Страница 13: ...taken into consideration when the connections of power cable are made such as the ambient temperature direct exposure to heat dirext exposure to sunlight The specifications for the power cable refer...

Страница 14: ...CLEARANCE REQUIRED AROUND UNITS SINGLE ZONE CLEARANCE REQUIRED AROUND UNITS DUAL ZONE Indoor unit B Indoor unit A SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainabl...

Страница 15: ...ndoor unit C SYSTEM LAYOUT INSTALLATION CLEARANCE Indoor unit A Indoor unit B Indoor unit C Indoor unit D SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainable and Ef...

Страница 16: ...screws Align mounting plate holes with those holes drilled on the wall and put anchors or screws into the holes to secure mounting plate STEPS TO MOUNT PLATE a b c Drill mounting holes to make sure a...

Страница 17: ...rear side of plastic casing Snap the plastic casing bottom into the mounting plate gently Sealed with putty Secure the piping wiring set with clamp Trim the extra portion 2 in or less from floor 18 18...

Страница 18: ...35 45 CONNECT REFRIGERANT PIPES BETWEEN INDOOR AND OUTDOOR UNITS Firstly connect copper tubes at indoor unit Bend pipes by tools but not by hands Extra length is needed for future service REFRIGERANT...

Страница 19: ...ipes Over length soft pipes will lead to irregular bending Undersize bending will damage the soft pipe Short soft pipes will have them bending undersize it s not allowed INLTS STRT COUP COUP H OFST EL...

Страница 20: ...ks 1 Blink lit for 0 5 sec then off for 0 5 sec then lit for 0 5 sec 2 E4 Code Outdoor ambient temperature is too low do not to run unit during severe cold weather Refrigerant at low level users need...

Страница 21: ...hnician to make appointment with YMGI tech support and call us while the techician is at job site 4 Better to check the unit get problems and model model and serial ready before calling YMGI tech supp...

Страница 22: ...STALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS IMPORTANT NOTES FOR INSTALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS YMGI Engineered Comfort Products for A Sustainable and Efficient...

Страница 23: ...original licensed installer or current service contractor should be contacted first of all since they installed the unit and or know more details than anybody else They will check the unit and find o...