No.
Name
Description
C6-02
Carrier Frequency
Selection
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User-defined (determined by C6-03
through C6-05)
Note:
Default setting value is
dependent on parameters
A1-02, Control Method
Selection and o2-04, Drive
Model Selection.
C6-03
Carrier Frequency
Upper Limit
Determines the upper and lower limits for
the carrier frequency.
Carrier Frequency
E1-04
Max Output
Frequency
Output Frequency
× (C6-05) × K
Output
Frequency
C6-03
C6-04
C6-04
Carrier Frequency
Lower Limit
C6-05
Carrier Frequency
Proportional Gain
d1-01 to
d1-04;
d1-16
Frequency Reference 1
to 4; 16
Sets the frequency reference for the drive.
Setting units are determined by parameter
o1-03.
d1-17
Jog Frequency
Reference
Sets the Jog frequency reference. Setting
units are determined by parameter o1-03.
d2-01
Frequency Reference
Upper Limit
Sets the frequency reference upper limit as
a percentage of the maximum output
frequency.
d2-02
Frequency Reference
Lower Limit
Sets the frequency reference lower limit as
a percentage of the maximum output
frequency.
d2-03
Master Speed
Reference Lower Limit
Sets the lower limit for frequency
references from analog inputs as a
percentage of the maximum output
frequency.
d3-01
Jump Frequency 1
Eliminates problems with resonant
vibration of the motor/machine by avoiding
continuous operation in predefined
frequency ranges. The drive accelerates and
decelerates the motor through the
prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥
d3-02 ≥ d3-03.
d3-02
Jump Frequency 2
d3-03
Jump Frequency 3
d3-04
Jump Frequency Width
Sets the dead-band width around each
selected prohibited frequency reference
point.
E1-01
Input Voltage Setting
This parameter must be set to the power
supply voltage.
WARNING! Electrical Shock Hazard.
Drive input voltage (not motor
voltage) must be set in E1-01 for the
protective features of the drive to
function properly. Failure to do so
may result in equipment damage
and/or death or personal injury.
No.
Name
Description
E1-03
V/f Pattern Selection
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f E1-04 through E1-13
settings define the V/f pattern
Note:
Parameter setting value is
not reset to the default
value when the drive is
initialized.
E1-04
Maximum Output
Frequency
These parameters are only applicable when
E1-03 is set to F.
To set linear V/f characteristics, set the
same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be
disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Note:
E1-07, E1-08, and E1-10
to E1-13 are not available
in OLV/PM control mode.
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-07
Middle Output
Frequency
E1-08
Middle Output
Frequency Voltage
E1-09
Minimum Output
Frequency
E1-10
Minimum Output
Frequency Voltage
E1-11
Middle Output
Frequency 2
E1-12
Middle Output
Frequency Voltage 2
E1-13
Base Voltage
E2-01
Motor Rated Current
Sets the motor nameplate full load current
in amps. Automatically set during
Auto-Tuning.
E2-11
Motor Rated Power
Sets the motor rated power in kilowatts (1
HP = 0.746 kW). Automatically set during
Auto-Tuning.
E5-02
Motor Rated Power
Sets the rated capacity of the motor.
E5-03
Motor Rated Current
Sets the motor rated current.
E5-04
Number of Motor Poles Sets the number of motor poles.
E5-05
Motor Stator
Resistance
Set the resistance for each motor phase.
E5-06
Motor d-Axis
Inductance
Sets the d-Axis inductance for the PM
motor.
E5-07
Motor q-Axis
Inductance
Sets the q-Axis inductance for the PM
motor.
E5-09
Motor Induction
Voltage Constant 1
Sets the induced peak voltage per phase in
units of 0.1 mV/(rad/s) [electrical angle].
Set this parameter when using an IPM
motor with variable torque.
Set E5-24 to 0 when setting this parameter.
E5-24
Motor Induction
Voltage Constant 2
Sets the induced phase-to-phase rms
voltage in units of 0.1 mV/(r/min)
[mechanical angle].
i.8 Parameter Table
72
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Содержание Z1000 CIMR-ZU*A Series
Страница 91: ......