Table i.19 SW1/SW2 Screw Sizes and Tightening Torques
Drive Model
SW1/SW2 Screw Size
Tightening Torque
2A0011
2A0017
4A0005
4A0008
4A0011
M3 × 16
0.5 to 0.6 N
•
m
2A0024
2A0031
4A0014
4A0021
4A0027
M3 × 16
0.5 to 0.6 N
•
m
2A0046
2A0059
4A0034
4A0040
4A0052
oo
B
M3 × 16
0.5 to 0.6 N
•
m
2A0075
2A0088
2A0114
4A0052
oo
A
4A0065
4A0077
4A0096
M5 × 30
2 to 2.5 N
•
m
–
4A0124
M5 × 25
2 to 2.5 N
•
m
2A0143
2A0169
2A0211
2A0273
4A0156
4A0180
4A0240
M5 × 25
2 to 2.5 N
•
m
–
4A0302
M5 × 25
2 to 2.5 N
•
m
u
Wiring Checklist
No.
Item
Page
Drive, Peripherals, Option Cards
1
Check drive model number to ensure receipt of correct model.
11
2
Make sure you have the correct noise filters and other peripheral devices.
–
3
Check the option card model number.
–
Installation Area and Physical Setup
4
Ensure that the area surrounding the drive complies with specifications.
13
Power Supply Voltage, Output Voltage
5
The voltage from the power supply should be within the input voltage specification range of the drive.
–
6
The voltage rating for the motor should match the drive output specifications.
11
7
Verify that the drive is properly sized to run the motor.
Main Circuit Wiring
8
Confirm proper branch circuit protection as specified by national and local codes.
–
9
Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3.
19
10
Properly wire the drive and motor together.
The motor lines and drive output terminals U/T1, V/T2, and W/T3 should match in order to produce the desired
phase order. If the phase order is incorrect, the drive will rotate in the opposite direction.
27
11
Confirm that the crimp terminals are in the correct position.
22
12
Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.
23
13
Use the correct wire gauges for the main circuit.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop
is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the
following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly.
23
14
For floating, impedance grounded, or asymmetrically grounded networks, disconnect the internal EMC filter by
moving the SW screw to the OFF position.
37
15
Properly ground the drive.
–
16
Tighten control circuit and grounding terminal screws.
23
i.4 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
39
Содержание Z1000 CIMR-ZU*A Series