Setting 3: Coast with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time
t
(C1-02) has expired. Cycle the Run command that was activated during time
t
after
t
has expired to start the drive.
Drive output shut off
Run wait time t
Run command
Output
frequency
ON
ON
ON
OFF
OFF
Figure i.49 Coast with Timer
The wait time
t
is determined by the output frequency when the Run command is removed and by the active deceleration time.
Min output
frequency
100%
(Max output
frequency)
Output frequency
when Stop command
was entered
Run wait time t
Active deceleration time
Momentary Power Loss
Minimum Baseblock
Time (L2-03)
Figure i.50 Run Wait Time Depending on Output Frequency
n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
Parameter Name
Setting Range
Default
b1-04
Reverse Operation Selection
0, 1
1
Setting 0: Reverse Enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse Disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
C1-01 to C1-04: Accel, Decel Times 1 and 2
Four different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched
automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).
Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02
are the default active accel/decel settings.
No.
Parameter Name
Setting Range
Default
C1-01
Acceleration Time 1
0.1 to 6000.0 s
30.0 s
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
i.5 Start-Up Programming and Operation
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
53