3 Electrical Installation
YASKAWA Europe
TOMP_C710606_75A V1000 IP66 - Quick Start Guide
EN 15
Control Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with screwless terminals.
There are three DIP switches, S1 to S3, located on the terminal board
Control Circuit Terminal Functions
NOTICE:
The terminals HC, H1, H2 can be used to disable the drive output. Other than in V1000 standard drives they can NOT be used to perform safe stop according to
EN60204-1 (Function is in preparation. Contact your sales representative or YASKAWA for details).
NOTICE:
The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
SW1
Switches analog input A2 between voltage and current input
SW2
Enables or disables the internal RS422/485 comm. port terminal resistance.
SW3
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires external 24 Vdc power supply)
Type
No.
Terminal Name (Signal)
Function (Signal Level), Default Setting
Multi-Function
Digital Inputs
S1
to
S6
Multi-function digital input 1 to 6
Photocoupler inputs, 24 Vdc, 8 mA
Note: Drive preset to sinking mode (NPN). When using source mode, set DIP switch
S3 to “SOURCE” and use an external 24 Vdc (±10%) power supply.
SC
Multi-function input common
Sequence common
Multi-Function
Analog/ Pulse
Inputs
RP
Pulse train input
Response frequency: 0.5 to 32 kHz, Duty: 30 to 70%, High: 3.5 to 13.2 V, Low: 0.0
to 0.8 V, input impedance: 3 k
:
)
+V
Analog input power supply
+10.5 V (max allowable current 20 mA)
A1
Multi-function analog input 1
0 to +10 Vdc (20 k
:
) resolution 1/1000
0/4 to 20 mA (250
:
) resolution: 1/500 (A2 only)
A2
Multi-function analog input 2
AC
Frequency reference common
0 V
Drive
Disable Inputs
HC
Drive Disable Input common
+24 V (max 10 mA allowed)
H1
Drive Disable Input 1
One or both open: Drive output disabled (time from input open to drive output
switch off is less than 1 ms)
Both Closed: Normal operation
H2
Drive Disable Input 2
Multi-Function
Relay Output
MA
N.O. (fault)
Digital relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
MB
N.C. output (fault)
MC
Digital output common
Multi-Function PHC
Output
P1
Photocoupler output 1
Digital photocoupler output
48 Vdc, 2 to 50 mA
P2
Photocoupler output 2
PC
Photocoupler output common
Monitor Output
MP
Pulse train output
32 kHz (max)
AM
Analog monitor output
0 to 10 Vdc (2 mA or less), Resolution: 1/1000 (10 bit)
AC
Monitor common
0 V
MEMOBUS/
Communication
R+
Communications input (+)
MEMOBUS/Modbus communication.:
RS-485 or RS-422, 115.2 kbps (max)
R–
Communications input (–)
S+
Communications output (+)
S–
Communications output (–)
Operator/ PC
Communication
RJ45
Communication port to Digital Operator
or PC
RS232: PC connection via JVOP-181 (USB Copy Unit), Digital Operators JVOP-180
(LCD) or JVOP-182 (LED). Other device connection may damage the drive or the
external device.Variant CIMR-...-0080 only on the drive. Variant CIMR-...-0081 with
external RJ45 connector.
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
R+ R- S+ S- IG
P1 P2 PC A1 A2 +V AC AM AC MP
MA MB MC
S1
S2
S3
Use a straght-edge screwdriver
with a blade width of max 2.5 mm
and a thickness of max 0.6 mm to
release the terminals
TOMP_C710606_75A_0_0_prePrint.pdf 47