Maintenance and Troubleshooting
Event Codes
There are three levels of event codes: Critical event, Warning event, and Information event.
Critical Events
Critical events: the inverter will cease producing AC power and cannot self-recover. This is indicated by the inverter
illuminating both the red Power Fault LED (triangle) and the yellow Maintenance LED (wrench). Note that some of these
Critical events can create a hazardous situation, indicated by DO NOT TOUCH.
DANGER
Ground Fault Hazard: Inverter enclosure is an electrical hazard.
DO NOT TOUCH: any equipment (including, but not limited to: the inverter, the PV array disconnect switch the PV array
combiners, the PV panels, or the PV racking system). Immediately contact the installer or another qualified person to
locate and repair the source of the ground fault.
Table 10-1 Critical Event Codes
CRITICAL
EVENT CODE
DISPLAY MESSAGE
DESCRIPTION
TROUBLESHOOTING
1
Software Parameter
Load Failure
An attempt to remotely download
software parameters has failed.
Attempt to update the firmware and
power cycle the inverter. Contact
Technical Support.
2
Internal
Communication 1
Failure
Internal communication failure
detected.
Attempt to update the firmware and
power cycle the inverter. Contact
Technical Support.
3
Internal
Communication 2
Failure
Internal communication failure
detected.
Attempt to update the firmware and
power cycle the inverter. Contact
Technical Support.
4
ARC Fault Detected
A DC series arc fault has been
detected in the PV array.
Inspect for and repair damage to the
PV array and DC wiring. Clear the ARC
Fault and retest. Contact Technical
Support.
5
AC Contactor Failure
One or both of the AC grid contactors
has failed. Contactors may fail open
or closed.
Power cycle the inverter. If the inverter
does not clear the error, contact
Technical Support.
6
Critical Over
Temperature
Internal hardware temperature has
exceeded the allowable limits.
Check to ensure external fans are clear
of debris and are operating.
-If external fans are not operating.
Contact Technical Support, fans may
need to be replaced.
7
Ground Fault,
Excessive Leakage
Current
A ground fault condition has been
detected. Leakage current is greater
than the allowable limit. Check the
DO NOT TOUCH any equipment
(including, but not limited to: the
inverter, the PV array disconnect