Figure 3-20 Mismatched String Sizes within a Zone or Inverter
DC Connection Specifications
The voltage rating of the DC conductors must meet or exceed 1000VDC. When connecting to the fuse holders, use copper
PV conductors. Fuse holders can accommodate conductor sizes ranging from 14 to 8 AWG (2.5 to 8.4 mm
2
). All electrical
conductors must meet the requirements of the NEC and local electrical codes.
Table 3-6 DC Input Specifications
DC INPUT
XGI 1000-60/60
XGI 1000-60/65
XGI 1000-65/65
MAXIMUM POWER INPUT VOLTAGE
RANGE
580-850 VDC
600-850 VDC
600-850 VDC
OPERATING VOLTAGE RANGE (MPPT)
350-950 VDC
350-950 VDC
350-950 VDC
MAXIMUM OPERATING INPUT
CURRENT
105.6 A
(26.4 A per zone)
105.6 A
(26.4 A per zone)
110.6 A
(27.65 A per zone)
MAXIMUM OPERATING PV POWER
(PER MPPT ZONE)*
15.3 kW
15.3 kW
16.6 kW
MAXIMUM RATED PV INPUT (PER
MPPT ZONE)*
22.5 kW
22.5 kW
24.4 kW
ABSOLUTE MAXIMUM INPUT
VOLTAGE
1000 VDC
1000 VDC
1000 VDC
NUMBER OF MPP TRACKING ZONES**
4 / 1
4 / 1
4 / 1
NUMBER OF PV SOURCE CIRCUITS
(FUSED INPUTS)
4 per MPPT zone;
16 total
4 per MPPT zone;
16 total
4 per MPPT zone;
16 total
MAXIMUM PV CURRENT (ISC X 1.25)
PER ZONE/SINGLE ZONE
50 A/180 A
50 A/180 A
50 A/180 A
MAXIMUM RECOMMENDED DC-TO-
AC RATIO
1.5
1.5
1.5
* Limits apply only to inverters in Independent Mode, for inverters operating in Combined Mode multiply limits by 4.
** Number of MPP Tracking Zones must be specified at the time of order.